INSIGHTS, RESEARCH | November 12, 2026

Fifteen Years of Exposure: What Supermarket Refrigeration Attacks Reveal About Industrial Cybersecurity

Key Takeaways

  • Cyberattacks against supermarket refrigeration systems across Europe in October and November 2026 demonstrate how the compromise of internet-connected operational technology (OT) can result in physical disruption and significant financial losses.
  • Internet-exposed industrial control systems are not a new problem. Research published in 2011 and the subsequent Project SHINE initiative identified widespread exposure of industrial equipment more than a decade ago.
  • Removing direct internet exposure through firewalls and secure remote access is an important mitigation, but does not eliminate the underlying security risks.
  • The December 2025 attacks against Polish renewable energy facilities demonstrate the limitations of perimeter security when firewalls are themselves inadequately secured and industrial equipment remains vulnerable.
  • Effective OT cybersecurity requires a combination of asset visibility, secure configuration, vulnerability management, network segmentation and ongoing assessment of both perimeter and internal systems.

A New Target, a Familiar Problem

During October and early November 2026, a series of cyberattacks targeted commercial refrigeration systems across Europe, affecting supermarkets and other food retailers. [7]

The initial incidents in France reportedly affected approximately 700 supermarkets. Subsequent attacks were reported in several European countries, including Ireland, Sweden, Belgium and the United Kingdom.

In these incidents, attackers gained unauthorised access to refrigeration management systems and manipulated operating parameters, including temperature setpoints and defrost functions. Some retailers reported refrigeration temperatures reaching 50°C, resulting in food spoilage, operational disruption and significant financial losses.

Although the investigation into these incidents remains ongoing, the attacks have drawn attention to the security of internet-connected refrigeration management equipment.

Modern commercial refrigeration systems commonly incorporate centralised management capabilities, allowing operators and maintenance providers to monitor temperatures, configure operating parameters, manage alarms and diagnose faults remotely.

These capabilities deliver tangible operational benefits, particularly for retailers managing large numbers of refrigeration units across geographically distributed locations.

However, they also introduce cybersecurity risks when management interfaces are exposed directly to the Internet or protected by inadequate security controls.

Security researchers have previously identified vulnerabilities in refrigeration management systems, including authentication bypass and command injection vulnerabilities affecting Danfoss AK-SM 800A controllers. [3]

While manufacturers have released updates addressing identified vulnerabilities, internet-wide research continues to identify exposed systems running outdated firmware.

The recent attacks illustrate an important distinction between conventional IT security incidents and attacks against OT.

The attacker does not necessarily need to compromise the physical equipment or exploit vulnerabilities in its underlying control logic.

Access to legitimate management functionality may be sufficient to manipulate the physical process and cause operational disruption.

More significantly, the underlying security weaknesses are not new.

Industrial Internet Exposure: A Problem Documented Since 2011

In June 2011, Eireann Leverett published Quantitatively Assessing and Visualising Industrial System Attack Surfaces, research examining the exposure of industrial control systems to the public Internet. [1]

Using historical data collected through Shodan, the research identified more than 7,500 internet-accessible industrial devices, including building management systems, HVAC controllers, meters and SCADA systems.

The research demonstrated that industrial equipment, often assumed to be isolated from external networks, was accessible through publicly routable internet connections.

It also explored the correlation between exposed devices, identifiable software and publicly documented vulnerabilities.

The objective was not simply to identify exposed systems, but to provide organisations with better visibility of their external attack surfaces and support the prioritisation of security improvements.

This work anticipated a challenge that continues to affect industrial cybersecurity: organisations cannot effectively protect systems they do not know are exposed.

The following year, Project SHINE (SHodan INtelligence Extraction), established by Rob Radvanovsky and Jake Brodsky, expanded this research. [2]

Project SHINE used Shodan to identify and catalogue internet-accessible industrial control systems. By the conclusion of its data collection in January 2014, the project had identified more than two million unique IP addresses associated with potentially relevant industrial equipment.

These figures require careful interpretation. An internet-accessible system is not necessarily vulnerable, and search-engine results do not provide a reliable measure of the total number of individual industrial devices.

Nevertheless, the research established that internet exposure was a widespread issue affecting multiple industrial sectors.

More than a decade later, the circumstances surrounding the supermarket refrigeration attacks suggest that many of the same challenges remain unresolved.

Industrial connectivity has expanded considerably, driven by remote maintenance requirements, centralised monitoring, operational efficiency and the increasing integration of IT and OT environments.

However, increased connectivity has not always been accompanied by equivalent improvements in cybersecurity governance, asset management or vulnerability remediation.

The result is an expanding population of connected industrial devices whose security may depend on outdated software, insecure configurations or insufficiently controlled remote access.

The Obvious Response: Secure the Network Perimeter

The immediate recommendation for organisations operating internet-exposed industrial equipment is straightforward: remove unnecessary direct access from public networks.

Industrial controllers, management interfaces and engineering services should not normally be directly accessible from the Internet.

Where remote access is operationally necessary, organisations should implement appropriately configured security controls, including firewalls, network segmentation and secure remote access mechanisms.

These measures can significantly reduce the attack surface by limiting the systems and services available to an external attacker.

However, a firewall should not be considered the endpoint of an organisation’s industrial cybersecurity strategy.

A firewall is itself a network-connected computing platform, potentially incorporating an operating system, web-based management interface, VPN services and other externally accessible functionality.

Like other software-based systems, it requires secure configuration, vulnerability management, authentication controls and ongoing maintenance.

Furthermore, while a firewall can restrict access to an industrial network, it does not automatically address vulnerabilities in the devices operating within that network.

Once an attacker obtains authorised or unauthorised access through the perimeter, weaknesses such as default credentials, insecure services and outdated firmware may remain exploitable.

The consequences of these overlapping weaknesses were demonstrated in the December 2025 attacks against Polish energy infrastructure.

Poland’s Renewable Energy Attacks: When the Perimeter Becomes the Attack Surface

On 29 December 2025, coordinated cyberattacks targeted multiple organisations within Poland’s energy and manufacturing sectors. [4]

According to a detailed technical report published by CERT Polska on 30 January 2026, the attacks affected at least 30 wind and photovoltaic installations, a combined heat and power plant, and a manufacturing organisation. [5]

At the renewable energy facilities, the attackers targeted grid connection points (GCPs), which provide the interface between generating facilities and electricity distribution networks.

These locations typically contain industrial automation equipment, including remote terminal units (RTUs), human-machine interfaces (HMIs), protection relays and communications infrastructure.

The attackers damaged multiple industrial devices, resulting in the loss of communications between affected facilities and their distribution system operators.

Although electricity generation continued and the attacks did not affect the stability of Poland’s electricity system, CERT Polska assessed that the attackers had obtained sufficient access to potentially disrupt generation at the affected facilities.

The incident provides a valuable case study in the limitations of relying primarily on perimeter security.

The Firewalls Were Present

CERT Polska reported that every affected renewable energy facility had a FortiGate appliance operating as both a firewall and VPN concentrator.

These systems were intended to provide controlled remote connectivity while protecting the internal industrial networks.

However, investigators identified several weaknesses in their deployment and maintenance.

All affected installations had internet-accessible VPN interfaces that permitted authentication without multifactor authentication.

Furthermore, some appliances had previously remained vulnerable to serious security flaws, including remote code execution vulnerabilities, for extended periods.

The report also highlighted the potential risks associated with reusing administrative credentials across multiple facilities.

Importantly, CERT Polska could not conclusively determine the initial compromise mechanism.

The attackers factory-reset the compromised FortiGate appliances, destroying logs and other information that could have established precisely how access was obtained.

Consequently, it would be inaccurate to conclude that exploitation of an unpatched FortiGate vulnerability was definitively responsible for the initial compromise.

Nevertheless, the investigation established that the attackers had obtained administrative access to the security appliances.

This access significantly undermined the protection offered by the network perimeter.

Segmentation Depends on the Security of Its Enforcement Points

Some of the affected facilities implemented network segmentation through separate VLANs.

While segmentation is an important industrial security control, its effectiveness depends on the integrity of the systems enforcing communication restrictions between network segments.

CERT Polska reported that the attackers possessed administrative privileges on the FortiGate devices and could therefore potentially access credentials permitting connectivity to multiple network segments or modify the firewall configuration to establish equivalent access.

In this situation, compromising the perimeter device created opportunities to bypass or undermine the network boundaries it was responsible for enforcing.

This illustrates a broader challenge associated with consolidating security functionality within a single appliance.

Where remote access, firewall enforcement and inter-network routing are managed by the same device, its compromise may have consequences across multiple security functions.

Organisations must therefore assess the security of network enforcement points with the same rigour applied to the industrial systems they protect.

Vulnerabilities Behind the Firewall

The Polish investigation also demonstrated that successful perimeter compromise was only one component of the attack.

After accessing the industrial networks, the attackers exploited insecure configurations and weak authentication controls across several types of industrial equipment.

CERT Polska documented multiple examples:

Hitachi RTU560 controllers: The attackers used default credentials to access controller management interfaces and upload deliberately corrupted firmware. This caused the affected devices to enter repeated reboot cycles, disrupting communication and remote control capabilities.

The investigation also found that secure firmware verification functionality, available on some affected devices, had not been enabled. Separately, some firmware versions were affected by CVE-2024-2617, a vulnerability capable of bypassing firmware verification.

Mikronika RTUs: Default root credentials enabled access to Linux-based controllers through SSH. The attackers subsequently executed destructive commands against the devices’ filesystems.

Hitachi Relion protection relays: Default FTP credentials permitted access to system files, which the attackers deleted. CERT Polska noted that following the manufacturer’s recommended deployment configuration would have disabled these accounts.

Moxa NPort serial device servers: Default credentials allowed attackers to modify device configurations, perform factory resets and assign unusable network addresses.

Windows-based HMIs: Common administrative passwords enabled the compromise of several HMI systems and the deployment of destructive malware.

One particularly revealing observation concerned facilities that did not use the same administrator passwords.

Where unique credentials had been configured, the attackers’ password-breaking attempts were unsuccessful, and the corresponding HMI systems were not damaged.

This provides a practical demonstration of the effectiveness of fundamental security controls.

Even during a coordinated, destructive attack against industrial infrastructure, relatively straightforward measures such as eliminating default credentials and implementing unique administrative passwords were sufficient to prevent some of the observed compromises.

The incident demonstrates two distinct but related risks.

First, an inadequately secured perimeter appliance can become an effective entry point into an otherwise segmented industrial network. Second, vulnerabilities and insecure configurations within that network remain significant risks regardless of the presence of perimeter security.

Protecting the network boundary is necessary, but it does not remove the requirement to secure the systems operating behind it.

Similar Weaknesses Identified During Wind Farm Security Assessments

The security weaknesses documented by CERT Polska are consistent with issues identified during real-world industrial cybersecurity assessments.

Research presented in ACME Windpharm – It Can’t Be ‘Smart’ If You Lack Simple Security explored vulnerabilities identified during wind farm security assessments, including insecurely configured network equipment, inadequate patching and excessive reliance on perimeter security appliances. [6]

The assessments highlighted the risks associated with deploying sophisticated security technologies without maintaining fundamental security practices.

Industrial networks may incorporate dedicated firewalls, managed switches and remote access infrastructure, yet still contain devices running vulnerable firmware or configured with insecure management services.

Similarly, security appliances may be deployed to protect critical systems without sufficient consideration of their own vulnerability exposure or ongoing maintenance requirements.

These weaknesses are particularly significant in distributed renewable energy environments.

Wind and solar installations commonly rely on remote communications infrastructure for monitoring, maintenance and interaction with distribution network operators.

Individual facilities may be geographically isolated, unmanned and maintained by multiple suppliers or service providers.

This introduces additional challenges around asset ownership, vulnerability management, access control and the consistent application of security requirements.

The Polish incidents demonstrate how these weaknesses can be combined during a real-world attack.

An attacker who compromises remote access infrastructure may subsequently exploit weaknesses in industrial controllers, communications devices and management systems.

Importantly, the vulnerabilities required for such attacks are not necessarily sophisticated or previously unknown.

Many arise from insecure deployment practices, missing security updates and inadequate access controls.

Moving Beyond Perimeter Security

The lessons from the refrigeration incidents and Polish energy attacks are relevant to organisations operating connected industrial systems across multiple sectors.

Effective protection requires a defence-in-depth approach that addresses both external exposure and internal security weaknesses.

1. Establish Visibility of Internet-Accessible Assets

Organisations need an accurate understanding of which industrial systems and management services are accessible from external networks.

This should include equipment installed or maintained by third parties, remote maintenance connections, cellular routers and other communications infrastructure that may not be managed by central IT teams.

External attack surface assessments can help identify undocumented or unintended exposure.

Importantly, this should be an ongoing activity rather than a one-time exercise.

2. Secure Remote Access Infrastructure

Firewalls, VPN concentrators and other remote access technologies should be managed as security-critical assets.

Controls should include:

  • Timely security updates and vulnerability remediation.
  • Multifactor authentication for remote access.
  • Restricted management interfaces and administrative privileges.
  • Unique credentials across sites and systems.
  • Network access limited to specific operational requirements.
  • Centralised logging and monitoring, with records protected from deletion following appliance compromise.

Where feasible, remote maintenance access should be restricted to authorised users and activated only when operationally required.

3. Assess Security Beyond the Perimeter

Network segmentation reduces exposure but does not eliminate vulnerabilities within protected environments.

Organisations should assess industrial controllers, HMIs, engineering workstations, communications devices and other operational assets for insecure configurations and known vulnerabilities.

Particular attention should be given to default credentials, unnecessary services, outdated firmware and insecure management protocols.

Security assessments should also examine whether compromise of a remote access service would provide excessive access to otherwise separated systems.

4. Implement Risk-Based Vulnerability Management

Patching industrial systems presents operational challenges that differ from those encountered in conventional IT environments.

Updates may require testing, planned maintenance windows or coordination with equipment manufacturers.

Some industrial products may have limited support lifecycles or dependencies that prevent immediate remediation.

However, these constraints reinforce the need for structured vulnerability management rather than removing it.

Where vulnerabilities cannot be promptly remediated, organisations should implement appropriate compensating controls, document residual risks and establish clear ownership of the remediation process.

5. Validate Recovery and Operational Resilience

The Polish attacks demonstrate that attackers may deliberately destroy device configurations, firmware and local system data to complicate recovery.

Industrial incident response planning should therefore consider more than restoring conventional IT services.

Organisations should maintain protected backups of device configurations and firmware, verify their restoration procedures, and establish how critical industrial processes can be operated or recovered when remote management infrastructure is unavailable.

For refrigeration environments, additional consideration should be given to independent temperature monitoring, alarm systems and operational safeguards capable of detecting or limiting unauthorised changes to control parameters.

The objective is not only to prevent compromise, but also to reduce its potential physical consequences.

The Continuing Challenge of Industrial Cybersecurity

The recent supermarket refrigeration attacks illustrate how increasingly connected industrial systems can expose organisations to operational and financial risks.

However, the underlying security challenges have been understood for more than fifteen years.

Research in 2011 demonstrated that industrial equipment was accessible from the public Internet.

Project SHINE subsequently highlighted the scale of industrial internet exposure.

More recent industrial security assessments have continued to identify weaknesses involving vulnerable network appliances, insecure configurations and inadequate access controls.

The December 2025 attacks against Polish renewable energy infrastructure demonstrated the consequences when attackers successfully exploit combinations of these weaknesses.

The common theme is not simply that industrial devices are connected to the Internet.

Remote connectivity is often an essential operational requirement.

Rather, it is that connectivity must be accompanied by security controls appropriate to the criticality and operational characteristics of the systems involved.

Installing a firewall can significantly reduce exposure, but the firewall must itself be secured, and the systems behind it must not be assumed secure simply because external access is restricted.

The most effective approach combines asset visibility, secure remote access, vulnerability management, network segmentation, system hardening and validated recovery capabilities.

Fifteen years after researchers first demonstrated the scale of internet-exposed industrial infrastructure, the challenge is no longer establishing that the problem exists.

It is ensuring that organisations consistently implement and maintain the controls needed to address it.

References

[1] Eireann Leverett, Quantitatively Assessing and Visualising Industrial System Attack Surfaces, University of Cambridge, June 2011. https://www.cl.cam.ac.uk/~fms27/papers/2011-Leverett-industrial.pdf

[2] Project SHINE, Findings Report, Infracritical, 2014. https://infracritical.com/p/project-shine-findings-report-1oct2014.pdf

[3] Claroty Team82, Freeze the Controller, Defrost the Food: Uncovering Vulnerabilities in Danfoss Refrigeration Controllers, August 2026. https://claroty.com/team82/research/freeze-the-controller-defrost-the-food-uncovering-vulnerabilities-in-danfoss-refrigeration-controllers

[4] John O’Mahoney – IOActive Inc, Lessons from the Polish Energy Sector Incident, July 2026. https://www.ioactive.com/lessons-from-the-polish-energy-sector-incident/

[5] CERT Polska, Energy Sector Incident Report – 29 December 2025, published 30 January 2026. https://cert.pl/uploads/docs/CERT_Polska_Energy_Sector_Incident_Report_2025.pdf

[6] CS3STHLM, ACME Windpharm – It Can’t Be ‘Smart’ If You Lack Simple Security, presentation by Colin Cassidy. https://4sics.se/program/presentations/colin-cassidy/

[7] Reuters, Associated Press and RTÉ, reporting on European supermarket refrigeration cyberattacks, October–November 2026. https://www.reuters.com/business/retail-consumer/temperature-soars-swedish-grocery-store-freezers-one-store-blames-hackers-2026-11-02/

INSIGHTS | November 5, 2026

Cybersecurity Trends 2027: Risks Reshaping Security

Cybersecurity Trends 2027: Risks Reshaping Security

Key Takeaways

  • AI will expand security exposure through speed, scale, data access, and automated action. Its use requires clear operating boundaries.
  • Connected technologies will extend enterprise exposure through IoT, IIoT, OT, edge systems, cellular modems, and supplier-managed access.
  • Critical infrastructure security will be measured through continuity, safety, recovery time, and the ability to maintain trusted operations.
  • Offensive security will test whether controls perform across realistic attack paths, detection events, response decisions, and recovery actions.
  • Supply chain risk will require evidence across software, hardware, firmware, data, cloud services, and specialist providers.

Five shifts will define cybersecurity trends 2027: bounded AI, connected technologies, critical infrastructure exposure, offensive validation, and supply chain risk. Recent CISA alerts put those shifts in operational terms. In July 2026, CISA warned that threat actors were targeting internet-exposed programmable logic controllers in water systems. In August, a related advisory described actors using AI-generated exploitation scripts against exposed PLCs.

These incidents show why 2027 planning must connect emerging technology to evidence about real-world exposure. A joint Five Eyes statement warns that frontier AI is changing cyber risk on a timeline measured in months, not years. The following sections examine the five shifts most likely to affect enterprise exposure and the planning questions security leaders should use for 2027.

TrendWhere exposure is movingPlanning changes for 2027Priority validation question
Bounded AIModels, agents, data, tool access, and deployment pipelinesDefine permitted actions, data boundaries, human review, and rollback pathsCan the system fail safely when inputs, permissions, or model behavior change?
Connected technologiesIoT, IIoT, OT, edge systems, cellular modems, and supplier-managed accessMaintain an accurate external exposure register and secure remote accessWhich assets are reachable, who can reach them, and what can they change?
Critical infrastructureOperational systems with safety, uptime, and public-service consequencesLink cyber risk to continuity plans, engineering constraints, and recovery timeWhat is the operational consequence of compromise, lost visibility, or lockout?
Offensive securityIdentity, cloud, endpoints, applications, physical access, and response processesTest realistic attack paths, detection, response, and recoveryCan defenders contain an intrusion before it reaches a critical business process?
Supply chain riskOpen-source software, firmware, silicon, cloud services, integrators, and dataDemand evidence across suppliers and lifecycle stagesWhich dependency could change the trust boundary without internal approval?

This is a categorized risk map, not a ranked list. Its purpose is to show where enterprise exposure is moving and which validation question belongs to each trend. The first priority is AI, where adoption speed can exceed assurance.

AI will remain central to the cybersecurity trends shaping 2027. The useful question is where AI can act, what it can access, how its output is verified, and how quickly a human or system can stop it.

The World Economic Forum’s Global Cybersecurity Outlook 2026 found that 87% of respondents viewed AI-related vulnerabilities as the fastest-growing cyber risk during 2025. The report also found that 64% of organizations had a process to assess AI tools before deployment. Those figures point to a control gap between adoption and assurance. In 2027, that gap is likely to matter more as organizations connect AI to sensitive data, business workflows, and automated actions.

For 2027, AI security should be governed as an engineering discipline. Security teams need threat models for model inputs, training data, retrieval sources, plugins, APIs, identities, and automated actions. They also need operational tests for degraded performance, malicious instructions, data leakage, and unsafe tool use.

AI security lens: the 2027 shift

  • Authority: By 2027, define which actions require human approval and which actions can run automatically.
  • Data: By 2027, map sensitive data into prompts, context windows, training sets, logs, and model outputs.
  • Recovery: By 2027, maintain a tested rollback path for model, prompt, policy, and integration changes.

By 2027, bounded AI should distinguish durable security controls from product hype. Teams that can define authority, data boundaries, and recovery paths will be better positioned to deploy AI without turning speed into unmanaged exposure. That shift creates a bridge to the next priority: connected technologies and the paths they create into enterprise operations.

Connected Technologies Will Turn Asset Visibility Into Resilience

The attack surface in 2027 will extend to systems that many enterprise security teams do not directly own. Cellular modems, engineering workstations, cloud control planes, embedded devices, smart facilities, and supplier-managed connections can provide entry points to high-consequence environments.

CISA’s Internet Exposure Reduction Guidance states that internet-accessible IT, IIoT, SCADA, ICS, and remote access technologies continue to grow. The guidance recommends identifying accessible systems, removing unnecessary exposure, securing necessary remote access, and reviewing exposure on a routine basis.

The broader lesson applies across industries. Asset inventories need ownership, reachability, software and firmware status, remote-access paths, and operational consequences. A vulnerability register without exposure context will struggle to rank the paths that matter most.

Connected technology lens: the 2027 shift

  • Reachability: By 2027, identify every internet-facing asset, remote-access method, and supplier-managed connection.
  • Change authority: By 2027, record who can alter configuration, credentials, logic, firmware, or network paths.
  • Consequence: By 2027, map each asset to safety, uptime, revenue, regulatory, and recovery requirements.

By 2027, exposure management will need to move from periodic discovery to a continuous view of how technology connects to operations. That means tracking reachability, change authority, and consequence as conditions change—not only when an inventory is refreshed.

Critical Infrastructure Risk Will Be Measured in Operational Consequence

Critical infrastructure operators carry security requirements that extend beyond data protection. A compromised system can affect safety, public services, production, environmental controls, or the ability to operate manually during recovery.

CISA’s July 2026 alert reported that threat actors targeting exposed PLCs had modified passwords, changed IP addresses, and caused loss of monitoring and control functionality. The alert also warned that exposed OT assets can create risks involving operational disruption and physical damage. That pattern is expected to remain relevant in 2027 as exposed OT assets, remote access, and internet-connected control systems continue to create paths into operational environments.

For 2027, security planning should connect technical controls to engineering constraints and recovery time. Leaders need to know which systems can be isolated, which processes can run manually, which backups are trusted, and which suppliers can restore affected equipment.

Critical infrastructure lens

  • Continuity: Identify the essential process that must continue during a cyber incident.
  • Safety: Map how loss of control, visibility, or configuration integrity could affect people and equipment.
  • Recovery: Test restoration procedures against actual dependencies, access requirements, and operating conditions.

This perspective gives critical infrastructure risk a measurable business context. It also creates the basis for offensive testing that reflects real operational pressure.

Offensive Security Will Test Control Performance

Security programs increasingly need evidence that controls work under pressure. A tool deployment, policy document, or completed assessment provides limited assurance when teams have not tested a realistic attack sequence.

For 2027, mature programs will connect threat intelligence to threat emulation. The shift is from periodic, point-in-time testing to scenario-based validation of identity compromise, cloud privilege escalation, lateral movement, data access, physical entry, and recovery decisions in environments that reflect the organization’s technology and operating model.

Red and purple team exercises can reveal detection gaps, response delays, authority problems, and process constraints. In 2027, those exercises will need to connect more directly to business-critical outcomes, while penetration testing continues to examine technical weaknesses across applications, infrastructure, cloud, mobile, and embedded systems.

Offensive security lens: the 2027 shift

  • Path: Can an attacker move from an exposed service to a critical business process?
  • Signal: Which attacker actions create useful telemetry, and how long does triage take?
  • Decision: Who can isolate systems, suspend access, or accept operational impact during an incident?

By 2027, security testing should function as a management instrument, producing evidence for investment, prioritization, and risk acceptance—not simply a list of technical findings.

Supply Chain Risk Will Reach Below the Application Layer

Supply chain risk will continue to expand across software, hardware, firmware, cloud services, data, and specialist providers. The World Economic Forum’s 2026 report identifies supply chain opacity and concentration as core forces shaping cyber resilience.

For 2027, third-party risk programs will need to examine how dependencies are built, updated, configured, and retired. That includes open-source packages, CI/CD runners, model repositories, semiconductor components, device firmware, managed service accounts, and the people who maintain them.

The practical test is traceability. Security leaders should know which dependencies support critical processes, which parties can change them, what evidence supports their security, and how the organization will operate if a dependency becomes unavailable or untrustworthy.

Supply chain risk lens: the 2027 shift

  • Provenance: Can the organization verify where software, firmware, data, and components originated?
  • Privilege: Which suppliers, integrators, and service accounts can change production systems?
  • Continuity: What is the tested fallback if a provider is compromised, unavailable, or subject to geopolitical disruption?

By 2027, supply chain programs will need to move beyond point-in-time reviews toward evidence of provenance, privilege, and continuity across the dependency lifecycle. The resulting program connects procurement, architecture, engineering, incident response, and executive risk decisions.

What Security Leaders Should Prepare for in 2027

A strong 2027 security strategy will be built around validation. Set a short list of high-consequence scenarios, then test the assumptions behind them. Confirm that teams can see the relevant activity, make decisions quickly, and recover without relying on undocumented expertise.

2027 readiness check

  • Evidence: Can leaders see proof that priority controls work under realistic conditions?
  • Exposure: Can teams identify reachable assets, trust paths, and high-consequence dependencies?
  • Consequence: Can the organization contain disruption and recover within its operational limits?

How IOActive Can Help Prepare for 2027

IOActive’s analysis of the Five Eyes cyber risk statement identifies practical actions for organizations looking to minimize risk in 2027: reduce attack surface, accelerate patching, address legacy systems, strengthen identity and access controls, and prepare for incidents.

A research-led security partner can extend that work across AI, software, hardware, connected technologies, and critical infrastructure. IOActive’s AI/ML Security Services assess AI systems across architecture, code, applications, devices, and infrastructure. Its Red Team and Purple Team Services examine realistic attack paths and defensive response. Its penetration testing practice applies attacker perspective across cloud, mobile, embedded, infrastructure, and web services.

Build 2027 priorities around evidence, exposure, and operational consequence. To discuss an independent assessment of emerging risk, contact IOActive’s security experts and turn cybersecurity trends 2027 into a testable security plan.

Sources

INSIGHTS | September 25, 2026

One Exposure, Many Actors: What the NCSC’s OT Alert Adds to the AA26-097A Picture

Key Takeaways

  • On 27 August 2026, the NCSC published an Alert warning of increased targeting of operational technology (OT) systems across multiple sectors globally, including in the UK, carried out by a range of threat actors and resulting in some limited real-world disruption [1].
  • The Alert is deliberately unattributed. It should not be read as an extension of joint advisory AA26-097A, which attributes a separate and well-documented PLC exploitation campaign to Iranian-affiliated actors [2].
  • Three separate bodies of reporting published between April and August 2026, covering Iranian-affiliated PLC exploitation, Russian FSB Centre 16 router targeting, and unattributed activity against water sector controllers, converge on the same access route of systems reachable directly from the public internet.
  • The FBI and EPA have reported that similarities in network configurations supplied by third parties allowed attackers to repeat successes across multiple victims, making integrator and supplier architecture a first-order concern rather than a downstream one [3].
  • The Alert lands five days before the UK Cyber Security and Resilience Bill reaches Lords Committee Stage on 1 September 2026, placing OT exposure in front of regulators, boards and legislators simultaneously [4].

Why the NCSC’s Alert Matters Now

The NCSC classified its 27 August publication as an Alert rather than guidance. That distinction carries weight. The organisation states that it has been engaging with affected sectors directly in response to recent targeting and is publishing the material to support national resilience efforts, which indicates that the advice follows live incident handling rather than horizon scanning [1].

The substance is uncomfortable for anyone who has treated OT exposure as a solved problem. The NCSC reports increased targeting of OT systems across multiple sectors globally, including in the UK, conducted by a range of threat actors, with some limited real-world disruption already recorded [1]. It also sets out a broader judgement. Against a backdrop of technology-enabled uplifts in offensive capability and increased geopolitical instability, the threat from state use of offensive cyber, including outside of conflict, has almost certainly increased [1].

The timing compounds the message. The Alert arrives within four months of joint advisory AA26-097A, seven weeks after an international advisory on Russian state targeting of network devices, and four weeks after an FBI and EPA announcement describing degraded water operations in at least seven US states [2][3][5]. Regulators are moving in parallel. The Cyber Security and Resilience Bill is scheduled to enter Lords Committee Stage on 1 September 2026, with Royal Assent expected later in the year [4].

What Does the NCSC Alert Actually Say?

The Alert sets out eight actions. Several restate established practice:

  • Build a definitive view of OT architecture including all assets, communications pathways and external connections
  • Replace default credentials and enforce unique administrator accounts with multi-factor authentication where supported
  • Harden the OT boundary and keep gateways, firewalls, routers and remote access appliances within vendor support
  • Segment OT, management and business networks
  • Maintain tested, ransomware-resistant backups of configurations, controller logic and critical engineering data [1]

Two items deserve closer attention because they move beyond network-layer control.

The first concerns device state. The NCSC advises that OT devices be operated in a condition that prevents remote programming during normal operations, ensuring PLCs are not left in PROGRAM or other maintenance modes and that controller logic uses password-based write protection or equivalent mechanisms to prevent unauthorised changes from malicious endpoints [1]. This is a control on the device itself, not on the path to it, and it assumes the network boundary may fail.

The second concerns protocols. The Alert recommends migrating industrial protocols to secure variants where available, naming DNP3 to DNP3-SAv5, CIP to CIP Security, Modbus to Modbus Security, and OPC DA to OPC UA, while removing telnet and SNMP versions 1 and 2 from management use [1]. Where no secure alternative exists, insecure protocols should be confined to isolated network segments.

The Alert also addresses organisations without OT estates, noting a continuing pattern of disruptive activity against internet-exposed systems and edge devices across all sectors, and directing readers to maintain an accurate inventory of internet-facing systems, retire end-of-life equipment and monitor for unexpected configuration changes or outbound connections [1]. It points UK organisations towards the NCSC’s free Early Warning service and frames the Cyber Assessment Framework as the mechanism through which boards should seek assurance [1].

Notably, the Alert names no threat actor.

How Does This Connect to AA26-097A, and Where Does It Not?

This is the point at which analysis most often goes wrong, and the distinction matters more than the similarity.

Advisory AA26-097A, first published on 7 April 2026 and updated on 22 July 2026, attributes an active campaign to Iranian-affiliated APT actors exploiting internet-connected PLCs across US critical infrastructure. The July update broadened the observed manufacturer scope from Rockwell Automation/Allen-Bradley to include Schneider Electric and Siemens controllers, added detection guidance for malicious changes in reusable code modules within Rockwell PLC programs, and brought the Department of the Treasury onto the authoring byline alongside CISA, the FBI, NSA, EPA, the Department of Energy and US Cyber Command’s Cyber National Mission Force [2].

Separately, an international advisory published in July 2026, co-sealed by the NCSC alongside 18 partner agencies from 12 countries, attributes sustained targeting of poorly configured routers to Russian Federal Security Service Centre 16, tracked variously as Berserk Bear, Energetic Bear, Dragonfly, Ghost Blizzard and Static Tundra. That activity centres on internet-wide scanning for devices accepting default or weak SNMP community strings, followed by exfiltration of device configuration files [5].

Separately again, the FBI and EPA issued a public service announcement on 30 July 2026 describing unattributed malicious cyber actors targeting internet-facing Rockwell Automation/Allen-Bradley MicroLogix 1100 and 1400 PLCs. Water and wastewater utilities in at least seven states reported incidents from 27 July 2026 onwards. The actors changed device IP addresses and set passwords, producing loss of view and, in some cases, loss of function. Reported operational effects included loss of pressure and flooding, with the announcement noting that pressure loss in water systems could potentially allow untreated groundwater to seep into pipes [3].

Four publications carry three different attribution states. One names Iranian-affiliated actors, one names a Russian intelligence unit, and two describe activity the authoring agencies have chosen not to attribute. Collapsing these into a single narrative would be an analytical error, and one that regulated operators cannot afford to make in reporting or board briefings.

What survives the separation is the access route. In every case the initial condition is the same, namely a control system, a management interface or an edge device reachable from the public internet and frequently protected by default, weak or absent credentials. The NCSC’s phrasing, that this activity is being carried out by a range of threat actors, is the more useful framing for defenders precisely because it removes the actor from the risk calculation. Exposure is exploitable by whoever finds it first.

Who is Affected by the NCSC’s OT Alert?

CNI operators with field-deployed OT

Any organisation with internet-exposed OT could be affected. The NCSC is explicit that organisations should not assume their OT is inaccessible from the internet without verifying it, since unintended exposure can arise through misconfigurations, legacy connections or unmanaged assets [1]. Water, wastewater and energy operators with geographically distributed sites and cellular field connectivity carry the highest concentration of this risk.

System integrators and managed service providers

The FBI and EPA observed that across several victims, similarities in network setups provided by third parties may give attackers the opportunity to multiply successes where vulnerable configurations recur across a supplier’s customer base [3]. A single integrator’s default deployment pattern becomes a repeatable attack template. This finding maps directly onto the critical supplier designation powers in the Cyber Security and Resilience Bill.

Organisations without OT

The Alert is explicit that the broader pattern of disruptive activity against internet-exposed systems and edge devices affects all sectors [1]. Routers, firewalls, VPN concentrators and remote access appliances present the same fundamental exposure.

Boards and regulated entities across jurisdictions

UK operators face the CAF as the assurance framework of record and the Cyber Security and Resilience Bill as the coming statutory instrument [1][4]. EU operators are working to NIS2. US operators sit within the CISA advisory and directive framework, including binding requirements on end-of-support edge devices [6]. The technical remediation is common across all three, and only the reporting obligations differ.

What Makes This Exposure So Difficult to Eliminate?

The mitigations in the NCSC Alert are not novel, and that is the difficulty. Every one of the eight actions was recognised practice before August 2026. Their repeated publication indicates a gap between recommendation and implementation rather than a gap in knowledge.

Three factors sustain that gap.

Asset visibility remains hard in OT. Exposure is frequently unintended, arising from a commissioning shortcut, a supplier’s remote support link, or a cellular modem installed to solve an operational problem years earlier. An operator can hold an accurate architecture diagram and still be exposed through an asset that diagram never captured.

Integrity attacks defeat availability-focused monitoring. AA26-097A describes actors using legitimate vendor engineering software to alter controller logic and falsify operator displays, and the FBI reported at least one organisation discovering modified PLC project files after noticing ladder logic discrepancies across several sites [2][3]. Where the control room’s picture of the process is itself manipulated, conventional uptime monitoring will report normality.

Remediation carries operational cost. Removing a PLC from direct internet exposure, migrating a protocol, or replacing an end-of-life gateway involves planned downtime in environments where downtime is the primary risk being managed. This is where technical recommendation meets capital planning, and where accountability for the outcome frequently disperses.

How IOActive Can Help

The NCSC’s Alert describes a condition rather than an incident. That condition is assets reachable from the internet that the owner did not know were reachable, protected by credentials the owner did not know were still default. Verifying that condition is an assessment problem before it is a remediation problem, and it spans the OT estate, the edge estate and the third parties with standing access to both.

IOActive has operated in industrial control environments since building the first proof-of-concept worm against the smart grid in 2009 [9], and has helped define standards and best practices including NIST 800-53 and 800-37. The services below map to the specific gaps this Alert exposes.

Full Stack Security Assessments

The Alert’s first action, to build a definitive view of OT architecture and not assume OT is unreachable without verifying it, is precisely the work most assessments stop short of. Our Full Stack assessments examine the whole environment rather than a single layer, covering internet-facing controllers and HMIs, the OT/IT boundary, the cellular modem paths that frequently provide field sites with their only route to the internet, and the firmware and silicon of the devices themselves through penetration testing, reverse engineering, side-channel analysis and fault injection.

Two of the Alert’s actions sit at the device rather than the network layer. Those are confirming controllers are not left in PROGRAM mode, and migrating industrial protocols to secure variants such as DNP3-SAv5, CIP Security, Modbus Security and OPC UA. These are testable conditions, not policy statements, and they are where an assessment either produces evidence or produces reassurance. As we set out in Cyber Attack Trends 2026, the environments organisations depend on most are routinely the ones they monitor least.

Supply Chain Integrity

The FBI and EPA finding that similar third-party network configurations allowed attackers to repeat successes across a supplier’s customer base is the most consequential detail in the current reporting, and the least addressable by any single operator acting alone [3]. It also has a direct precedent in our analysis of the Polish energy sector incident, which documented more than 30 facilities breached through the same pattern of internet-facing VPN portals without MFA, where credential reuse across sites turned one compromised account into a fleet-wide problem.

Our Supply Chain Integrity work assesses the security posture of technology providers and critical third parties, covering firmware, embedded systems, remote access arrangements and procurement processes, so that inherited risk is identified before it becomes a shared incident. For UK operators, this maps onto the critical supplier designation powers in the Cyber Security and Resilience Bill [4].

Red Team and Purple Team Services

The Alert notes that OT environments are typically static and predictable, which makes baseline monitoring highly effective at identifying unauthorised activity [1]. The question is whether a given deployment actually achieves that in practice. Adversarial testing is how an operator finds out before an adversary does, particularly against integrity attacks such as altered controller logic and falsified operator displays, which availability-focused monitoring is not built to catch. Our Purple Team work translates those findings into measurable detection improvements, and we set out the distinction between the two approaches in Red Team vs Penetration Testing.

Advisory Services

The eight actions in this Alert have all been published before, in various forms, and that is the problem worth solving. When we examined the Minnesota water utilities in When the Advisory Arrives First, the gap was not the absence of a warning but the absence of an owner for acting on it.

Our Advisory Services cover programmatic security review, security programme development and management, and Virtual CISO support. They turn an alert into a prioritised remediation plan with named accountability, and produce the evidence boards need for CAF or equivalent regulatory assurance. That work is increasingly shaped by converging regimes across all three jurisdictions, as we examined in our analysis of the UK Energy Sector Cyber Security Strategy and the Five Eyes statement on AI and cyber risk. The latter is directly relevant to the NCSC’s judgement here that technology-enabled uplifts in capability are part of why the threat has increased [1].

If you would like to discuss how your organisation’s internet-facing OT and edge exposure measures up against the activity described in this Alert, we welcome the conversation.

  1. Verify exposure rather than assuming its absence. Build or refresh a definitive view of the OT architecture covering all assets, communications pathways and external connections, and validate it against external scanning results rather than against documentation [1].
  2. Remove control system devices from direct internet reachability. Broker all remote access through a secure gateway or jump host so that OT is never directly exposed to external networks, and secure cellular modems used for field connectivity with strong authentication and logging [1][3].
  3. Eliminate default and shared credentials on OT and edge devices. Enforce unique administrator accounts, enable multi-factor authentication where supported, and use key-based authentication in preference to passwords where the protocol allows [1].
  4. Enforce device-level write protection. Confirm that PLCs are not left in PROGRAM or maintenance modes during normal operations and that controller logic is protected against unauthorised modification [1].
  5. Validate controller logic integrity. Use vendor integrity checking tools to compare running programs against known-good logic, and verify that backups are free of malicious logic before restoration [3].
  6. Retire or isolate end-of-support edge devices. Maintain a rolling replacement forecast reviewed against ownership and procurement, and apply compensating controls with firm decommission dates where replacement is delayed [3][6].
  7. Baseline and monitor OT network traffic. OT environments are typically static and predictable, which makes baseline monitoring effective at identifying communication with PLCs and HMIs from unexpected devices, networks or routes [1].
  8. Rehearse manual operation and recovery. Test the capability to revert to manual control, isolate affected systems and restore from trusted backups, and treat those exercises as evidence for CAF or equivalent regulatory assurance [1][3].

Conclusion

The NCSC’s August Alert does not describe a new technique, a new vulnerability class or a new adversary. It describes a durable condition that a widening set of actors continues to find and exploit, namely control systems and edge devices reachable from the open internet. The value in reading it alongside AA26-097A is not in merging the two, but in observing that campaigns with entirely different sponsors, objectives and levels of sophistication are arriving at the same door.

That has a practical consequence for how operators prioritise. Attribution shapes the diplomatic and sanctions response, but it does not change the remediation. An internet-facing PLC with a default password represents identical risk whether the entity that finds it is a state intelligence service or an opportunistic scanner. As the UK’s statutory regime moves towards Royal Assent and the EU and US frameworks tighten in parallel, the operators best positioned will be those who can evidence what they expose to the internet, and who owns the answer.

References

  1. National Cyber Security Centre, Disruptive cyber activity highlights risk from internet-exposed systems and edge devices, 27 August 2026. https://www.ncsc.gov.uk/news/disruptive-cyber-activity-highlights-risk-from-internet-exposed-systems-and-edge-devices
  2. CISA, FBI, NSA, EPA, DOE, US Cyber Command CNMF and Department of the Treasury, Joint Cybersecurity Advisory AA26-097A, Iranian-Affiliated Cyber Actors Exploit Programmable Logic Controllers Across US Critical Infrastructure, published 7 April 2026, updated 22 July 2026. https://www.cisa.gov/news-events/cybersecurity-advisories/aa26-097a
  3. Federal Bureau of Investigation and Environmental Protection Agency, Malicious Cyber Actors Targeting Water and Wastewater Sector Internet-Facing Programmable Logic Controllers, Causing Operational Disruptions, 30 July 2026. https://www.fbi.gov/investigate/cyber/alerts/2026/malicious-cyber-actors-targeting-water-and-wastewater-sector-internet–facing-programmable-logic-controllers-causing-operational-disruptions
  4. UK Parliament, Cyber Security and Resilience (Network and Information Systems) Bill, HL Bill 32, Lords Second Reading 14 July 2026, Committee Stage 1 September 2026. https://bills.parliament.uk/bills/4035
  5. National Cyber Security Centre, UK and Allies urge critical sectors to improve defences against Russian intelligence targeting, July 2026. https://www.ncsc.gov.uk/news/uk-and-allies-urge-critical-sectors-to-improve-defences-against-russian-intelligence-targeting
  6. CISA, Reducing the Attack Surface for End-of-Support Edge Devices and Binding Operational Directive 26-02. https://www.cisa.gov/resources-tools/resources/reducing-attack-surface-end-support-edge-devices
  7. NCSC-UK, FBI and CISA, Secure Connectivity Principles for Operational Technology. https://www.ncsc.gov.uk/collection/operational-technology/secure-connectivity
  8. National Cyber Security Centre, Cyber Assessment Framework. https://www.ncsc.gov.uk/collection/cyber-assessment-framework
  9. M. Davis, IOActive, Advanced Metering Infrastructure (Smart Grid) Device Security, Black Hat USA 2009. https://blackhat.com/presentations/bh-usa-09/MDAVIS/BHUSA09-Davis-AMI-SLIDES.pdf
INSIGHTS | September 17, 2026

Internet-Exposed OT: What the UK Generator Incident Tells CNI Operators About Attack Surface

Key Takeaways

  • A small UK power generator was reportedly forced offline for four days in July 2026. Press reporting attributes the incident to Iran-linked actors, but the UK government has confirmed only that an incident occurred, declining to attribute it or identify the facility.
  • The initial access vector has not been disclosed. Operators cannot map the incident to a specific product or vulnerability, and any vendor claiming otherwise is speculating.
  • CISA’s Internet Exposure Reduction Guidance, revised on 21 August 2026, sets out four steps for identifying and removing unnecessary internet exposure, alongside a discovery port list covering common OT and remote access protocols.
  • CISA observed malicious activity against more than 100 internet-exposed systems in the US Water and Wastewater Systems Sector during July 2026, commonly involving PLCs connected directly to cellular modems.
  • UK guidance and regulation already point in the same direction. The NCSC’s secure connectivity principles for OT and the DESNZ and Ofgem proposals for baseline cyber resilience requirements both target the exposure and boundary weaknesses that recur across these incidents.

Why Does Internet-Exposed OT Matter Now?

Two items arrived within days of each other in late August 2026. CISA revised its Internet Exposure Reduction Guidance on 21 August, anchoring the document in malicious activity it had observed against internet-exposed industrial systems the previous month [5]. The Telegraph reported the following day that hackers linked to Iran had forced a small British power generator offline for four days during July [1]. Britain briefed energy company chief executives on 24 August, and the Department for Energy Security and Net Zero wrote to companies advising them on next steps [2][3].

The proximity is coincidental. The underlying subject is not. CISA describes adversaries reaching controllers through connectivity that asset owners had not catalogued, and a UK generation asset has now lost four days of output to cyber activity. The common factor across both is not a particular adversary or a novel technique. It is attack surface that organisations created themselves and did not measure.

The wider trend line supports that reading. The NCSC’s chief executive told the RUSI Annual Security Lecture in June 2026 that around 75 per cent of cyber activity targeting UK critical infrastructure can be linked to state actors, and that the agency had managed more than 200 incidents affecting CNI and its wider ecosystem over the previous year [13].

For security leaders, the useful question is not whether Iran shut down a British generator. It is whether the organisation can demonstrate, with evidence rather than assumption, what of its own operational technology is reachable from the public internet.

What Is Known About the UK Generator Incident?

The facts that can be stated with confidence are narrow. The Telegraph broke the story on 22 August 2026, reporting that a cyber attack in July had forced a small British generator offline for four days [1]. The Financial Times, BBC and Guardian subsequently published accounts largely derived from the original reporting [4].

The UK government has confirmed that an incident occurred while declining to attribute it or identify the facility. A government spokesperson described the affected asset as a small-scale energy generator and stated that at no point was there a risk to the wider energy system [3]. Michael Shanks, the minister for energy, said the government and industry were treating the incident seriously and were working with regulators and the NCSC to assess threats and strengthen protections, adding that there was no threat to the wider grid and that nobody lost power [2].

Attribution to Iran therefore rests on press reporting rather than on any official assessment. The Iranian Embassy in London did not respond to requests for comment [7]. Little technical detail has emerged through official channels, and the initial access vector remains undisclosed [4].

That gap matters for defenders. Without a published vector, the incident cannot be mapped to a specific vulnerability or product, and no defensive shopping list follows from it directly. What the incident does establish is that a UK generation asset sustained four days of outage arising from cyber activity. That is a materially different proposition from the access-without-effect intrusions that have characterised much reported CNI targeting to date, and it is the part operators should brief upwards.

What Does CISA’s Internet Exposure Reduction Guidance Recommend?

In the absence of a disclosed vector, the most useful available material addresses the attack surface rather than the adversary. CISA’s guidance approaches this from the discovery end, setting out four steps:

  1. Assess current exposure by identifying which assets are reachable via the internet, using scanning tools and services to gain visibility of the organisation’s online footprint.
  2. Evaluate the necessity of that exposure, and remove or restrict access for assets that do not need to be internet-accessible.
  3. Mitigate risks to assets that must remain exposed, through default password changes, patching, replacement of unsupported devices, use of a jump host, ingress and egress monitoring, and multi-factor authentication.
  4. Establish routine assessments so that new exposures are identified as IT and OT environments evolve [5].

The guidance is anchored in observed activity rather than theory. CISA reports that in July 2026 it observed malicious cyber activity targeting more than 100 internet-exposed systems in the US Water and Wastewater Systems Sector, commonly involving programmable logic controllers connected directly to a cellular modem [5]. Threat actors remotely accessed those exposed PLCs, changed device IP addresses and passwords, and caused loss of monitoring and control functionality and, in some cases, operational disruption [5].

The cellular modem detail deserves attention. Connectivity installed by vendors or integrators for maintenance convenience frequently sits outside the corporate network and outside routine attack surface scanning. The controller is directly reachable while the organisation’s own exposure reporting shows nothing [5].

CISA also publishes a port list for discovery work, covering remote access services and OT protocols including Modbus on 502 to 507/TCP plus additional implementation ports, Niagara Fox on 1911/TCP and 4911/TCP, EtherNet/IP on 2222/UDP and 44818/TCP, DNP3 on 19999/UDP and 20000/TCP and UDP, OPC UA on 4840/TCP and 4843/TCP, and BACnet on 47808/TCP [5]. An open port is not itself evidence of compromise, but CISA advises that any internet-accessible OT or remote access service should be investigated and unnecessary exposure removed [5].

One point of discipline applies here. CISA does not attribute the July water sector activity to a named actor in this document. The description does resemble the Iranian-affiliated campaign against internet-exposed PLCs set out in advisory AA26-097A, which was updated on 22 July 2026 to add Schneider Electric and Siemens controllers alongside Rockwell, and which names the water and wastewater sector directly [6]. IOActive examined that update in Iranian-Affiliated Actors Expand PLC Targeting to Siemens and Schneider Electric. Resemblance is not attribution. CISA does not join the two, and operators briefing boards should be precise about the difference between an observed exposure pattern and an attributed campaign. Neither should be joined to the UK incident without evidence.

What Do UK Guidance and Regulation Already Require?

UK operators do not need to wait for American guidance to act, because equivalent direction already exists. The NCSC’s secure connectivity principles for OT address the same weaknesses, covering the requirement that OT devices are not directly exposed to the public internet, that management protocols and the OT boundary are hardened, that secure versions of industrial protocols are adopted where available, and that OT, management and business networks are segmented [8]. A worked example for the water sector was added to the collection on 11 August 2026, the first content authored by the Industrial Control System Community of Interest to appear on the NCSC website [9]. Separate NCSC guidance covers creating and maintaining a definitive view of OT architecture, which is the UK equivalent of CISA’s first step [10].

The regulatory position is also moving. DESNZ and Ofgem published their response on reshaping cyber regulation in downstream gas and electricity on 5 August 2026, confirming an intention to develop baseline cyber resilience requirements for all Ofgem licensees and to review which operators fall within the Network and Information Systems Regulations 2018 [11]. Ofgem will lead development of the detailed proposals, working with DESNZ and the NCSC.

The direction of travel matters for smaller generators in particular. The current regime concentrates obligations on the largest operators, while the incident reported in July involved a small asset. The Cyber Security and Resilience Bill would expand the existing framework, including powers intended to allow ministers to direct regulated organisations to take proportionate action where an imminent or live cyber threat puts national security at risk [12]. Shanks has also indicated that a wider Energy Resilience Strategy is due later in 2026 [7].

Operators should expect the compliance floor to rise. Building an accurate exposure picture now is cheaper than doing it under a regulatory deadline.

Who Is Affected by Internet-Exposed OT Risk?

Electricity generation and distribution operators

The UK incident involved a small generation asset, and that is the substance of the concern rather than a mitigating detail. A distributed generation fleet multiplies near-identical assets running comparable equipment sourced from a small pool of suppliers. A weakness that is inconsequential in one asset compounds when repeated across hundreds [7].

Water and wastewater utilities

CISA’s observation of more than 100 exposed systems in a single sector within one month indicates that exposure is systemic rather than exceptional [5]. Smaller utilities with limited engineering headcount are least likely to hold an accurate inventory of internet-facing assets.

Manufacturers and process industries

Nothing in the exposure problem is specific to CNI designations. Discrete manufacturing, chemicals, food production and building management run the same protocols on the same controllers, frequently with weaker segmentation and no regulatory driver.

Suppliers, integrators and maintenance providers

Cellular modems, remote access appliances and vendor support tunnels are installed for legitimate operational reasons and rarely appear in the asset owner’s exposure register [5].

Boards and audit committees

The question of what the organisation exposes to the internet is an assurance question rather than a technical one, and it is answerable with a number.

What Are the Challenges for Operators?

The published guidance is not technically demanding. The difficulty is organisational and operational.

Verification is harder than assertion. Most operators can state that their OT is segmented. Fewer can evidence that claim against an external view of their own address space, and fewer still have examined infrastructure introduced by vendors, contractors or legacy projects [5].

Patching carries operational and safety consequences. OT frequently runs software that cannot be updated remotely, and operators must weigh intervention against the risk that downtime itself creates a safety issue. Replacement programmes run for years, and exposure cannot simply be accepted in the interim. The workable response is to move carefully when changing the plant and quickly when reducing the risk around it.

Ownership is the recurring failure. Guidance of this kind repeats the same controls because no single person owns the outcome of knowing what the organisation exposes and acting when a scan flags the same default credential six months running.

Detection in OT is more tractable than in IT, and is routinely neglected. OT environments are typically static and predictable, which makes baseline monitoring effective at identifying unauthorised activity and misconfiguration [8]. Few operators exploit that property.

How Can IOActive Help?

The defining feature of this incident is that the vector is undisclosed. There is no patch to apply and no indicator to hunt for. What remains actionable is the attack surface itself, and establishing that is an assessment problem rather than a threat intelligence problem.

IOActive has worked in industrial control environments since building the first proof-of-concept worm against the smart grid in 2009 [14], and its team has contributed to standards and best practice including NIST 800-53 and 800-37. The services below address the gaps this incident and the accompanying CISA guidance expose.

Full Stack Security Assessments

CISA’s first step, and the NCSC’s guidance on maintaining a definitive view of OT architecture, both require an operator to establish what is reachable rather than to assert it [5][10]. Our Full Stack assessments examine the whole environment rather than a single layer, covering internet-facing controllers and HMIs, the OT and IT boundary, the cellular modem paths that frequently give field sites their only route to the internet, and the firmware and silicon of the devices themselves through penetration testing, reverse engineering, side-channel analysis and fault injection. Where an asset has lost four days of output and no vector has been published, that depth is what separates a finding from a reassurance.

Supply Chain Integrity

The activity CISA observed in the water sector involved controllers connected directly to cellular modems, which is connectivity the asset owner frequently did not commission and does not monitor [5]. Our Supply Chain Integrity work assesses the security posture of technology providers and critical third parties, covering firmware, embedded systems, remote access arrangements and procurement processes, so that inherited exposure is identified before it becomes a shared incident. For UK operators this maps onto the critical supplier designation powers in the Cyber Security and Resilience Bill [12].

Advisory Services

The regulatory floor is rising for precisely the class of asset involved here. DESNZ and Ofgem intend to develop baseline cyber resilience requirements for all Ofgem licensees and to review which operators fall within the NIS Regulations 2018 [11]. We examined what that direction of travel means for operators in The UK Energy Sector Cyber Security Strategy. Our Advisory Services cover programmatic security review, security programme development and management, and Virtual CISO support, turning an exposure picture into a prioritised remediation plan with named accountability and the evidence a board needs for CAF or equivalent regulatory assurance.

The water sector offers a useful contrast. While recent attention has centred on attacks against US water infrastructure, coverage of how UK water regulators are responding has been comparatively thin — despite water companies having been in scope of the NIS Regulations since 2018 and required to submit annual OT resilience risk assessments against the NCSC’s Cyber Assessment Framework. Ofwat’s lever here is largely financial: PR24 price control deliverables are tied to the Drinking Water Inspectorate’s regulation 18 notices, with penalties layered on top of any Inspectorate enforcement. What’s less visible, compared to Ofgem’s published guidance for energy OES, is an equivalent public baseline for water operators to work against — sector performance data isn’t published, and companies are largely left to interpret CAF outcomes on their own. That’s exactly the kind of gap our cross-industry ICS/OT experience is built to close.

If you would like to discuss how your organisation’s internet-facing OT exposure measures up against the activity described in CISA’s guidance, we welcome the conversation.

  1. Establish an external view of the estate. Use exposure discovery tooling to enumerate what is reachable from the public internet across known organisational IP space, rather than relying on the internal asset register as the source of truth [5].
  2. Reconcile the external view against the register. Treat every unexplained result as an incident precursor. The gap between the two views is the working measure of unmanaged exposure.
  3. Interrogate vendor and contractor connectivity. Identify cellular modems, support tunnels and remote access appliances installed outside change control, including those commissioned during legacy projects [5].
  4. Remove what is unnecessary and secure what remains. Route required remote access through a managed gateway, firewall or VPN rather than connecting directly to a PLC, HMI or RTU, and enforce unique credentials with phishing-resistant multi-factor authentication [5].
  5. Harden the OT boundary against the NCSC principles. Confirm that boundary devices are within vendor support, that management interfaces are unreachable from the internet, and that segmentation between OT, management and business networks is enforced rather than assumed [8].
  6. Verify controller state across the estate. Confirm that controllers are not left in programming or maintenance modes and that write protection is applied to control logic.
  7. Baseline OT network traffic. Establish what normal communication looks like and alert on attempts to reach controllers and HMIs from unexpected devices, networks or routes [8].
  8. Report exposure to the board as a measurable figure. Present the count of internet-facing OT assets, the proportion with a documented operational justification, and the trend across reporting periods, ahead of the baseline requirements now being developed by Ofgem [11].

Conclusion

The UK generator incident may never be attributed publicly with the confidence operators would prefer, and the vector may never be disclosed. Waiting for either would be a mistake, because the actions that reduce this risk do not depend on knowing who was responsible. Guidance on both sides of the Atlantic describes an attack surface that organisations create for themselves and can therefore measure and reduce for themselves. Four days of outage at a small generator is a manageable consequence for the grid as a whole; for the owner facing the remediation bill, the reputational fallout, and the regulatory scrutiny that follows, it is anything but manageable. The same weakness, repeated across a distributed estate and reached by an actor willing to cause visible disruption, stops being a grid-level inconvenience and becomes a systemic one. That asymmetry is sharper in the US, where water and electricity distribution are served by a much larger population of small, often municipally or cooperatively owned operators: a single incident is unlikely to trouble the wider grid or supply, but it can be existential for the operator itself. Further guidance and regulatory detail are expected through the remainder of 2026, and operators who can already answer the exposure question — at whatever scale they sit — will find the rest considerably easier.

References

  1. The Telegraph, “Iranian hackers shut down UK power plant”, 22 August 2026. https://www.telegraph.co.uk/news/2026/08/22/iranian-hackers-shut-down-uk-power-plant/
  2. Reuters, “UK briefs energy chiefs after Iran-linked cyber attack reports”, 24 August 2026. https://www.reuters.com/business/energy/uk-briefs-energy-chiefs-after-iran-linked-cyber-attack-reports-2026-08-24/
  3. CNBC, “Small UK power generator shut down after cyberattack linked to Iran”, 23 August 2026. https://www.cnbc.com/2026/08/23/small-uk-power-plant-shut-down-after-iran-linked-cyberattack-report.html
  4. SecurityWeek, “Iran-Linked Hackers Shut Down UK Power Plant for Four Days”, August 2026. https://www.securityweek.com/iran-linked-hackers-shut-down-uk-power-plant-for-four-days/
  5. Cybersecurity and Infrastructure Security Agency, “Internet Exposure Reduction Guidance”, revision date 21 August 2026. https://www.cisa.gov/resources-tools/resources/exposure-reduction
  6. CISA, FBI, NSA, EPA, DOE, CNMF and Department of the Treasury, “Iranian-Affiliated Cyber Actors Exploit Programmable Logic Controllers Across US Critical Infrastructure”, AA26-097A, updated 22 July 2026. https://www.ic3.gov/CSA/2026/260722.pdf
  7. Industrial Cyber, “UK power generator reportedly taken offline in Iran-linked cyberattack, raising energy security concerns”, 24 August 2026. https://industrialcyber.co/utilities-energy-power-water-waste/uk-power-generator-reportedly-taken-offline-in-iran-linked-cyberattack-raising-energy-security-concerns/
  8. National Cyber Security Centre, “Operational Technology: Secure connectivity principles”. https://www.ncsc.gov.uk/collection/operational-technology/secure-connectivity
  9. National Cyber Security Centre, “Water sector example added to the NCSC’s Secure connectivity principles”, 11 August 2026. https://www.ncsc.gov.uk/blogs/water-sector-example-added-to-the-ncscs-secure-connectivity-principles
  10. National Cyber Security Centre, “Operational Technology: Creating and maintaining a definitive view of your OT architecture”. https://www.ncsc.gov.uk/collection/operational-technology/definitive-architecture-view
  11. Department for Energy Security and Net Zero and Ofgem, “Whole energy cyber resilience requirements: reshaping cyber regulation in downstream gas and electricity”, government response, updated 5 August 2026. https://www.gov.uk/government/consultations/whole-energy-cyber-resilience-requirements-reshaping-cyber-regulation-in-downstream-gas-and-electricity
  12. UK Government, “Cyber Security and Resilience (Network and Information Systems) Bill: Power to direct regulated entities”, factsheet, updated 30 June 2026. https://www.gov.uk/government/publications/cyber-security-and-resilience-network-and-information-systems-bill-factsheets
  13. Royal United Services Institute, NCSC Chief Executive remarks, RUSI Annual Security Lecture, June 2026. https://www.rusi.org/news-and-comment/rusi-news/hostile-states-behind-75percent-cyber-attacks-uk-infrastructure-ncsc-ceo
  14. M. Davis, IOActive, “Advanced Metering Infrastructure (Smart Grid) Device Security”, Black Hat USA 2009. https://blackhat.com/presentations/bh-usa-09/MDAVIS/BHUSA09-Davis-AMI-SLIDES.pdf
INSIGHTS | August 18, 2026

The Five Eyes AI Shift in Cyber Risk Statement: What Industry Leaders Need to Know Now

Key Takeaways

  • On 22 June 2026, the leaders of the Five Eyes cyber security agencies issued a joint statement, The AI Shift in Cyber Risk: Why Leaders Must Act Now, warning that frontier AI is transforming cyber risk on a timeline measured in months, not years.
  • The statement is signed by the heads of the National Cyber Security Centre (NCSC, UK), Cybersecurity and Infrastructure Security Agency (CISA, US), National Security Agency (NSA, US), Australian Signals Directorate (ASD, Australia), Communications Security Establishment (CSE, Canada), and Government Communications Security Bureau (GCSB, New Zealand) — an unusually unified articulation of urgency from the Five Eyes partnership.
  • Cyber risk is explicitly reframed as a core business risk and board-level responsibility, not a technical issue to be delegated downward.
  • Five practical actions are prescribed: reduce attack surface, accelerate patching, address legacy systems, strengthen identity and access controls, and prepare for incidents before they happen.
  • The statement lands days after the NCSC’s own CEO disclosed that 75% of attacks on UK critical infrastructure over the past year are linked to hostile states, and weeks after NCSC guidance warning of an incoming “vulnerability patch wave” driven by AI-accelerated exploitation.
  • Organisations that treat this as a compliance afterthought will be out of step with where their regulators, and their adversaries, are already heading.

A Statement for a Narrowing Window

Joint statements from the Five Eyes cyber agencies are not issued lightly, and this one is notable for its tone as much as its content. Published on 22 June 2026, The AI Shift in Cyber Risk [1] is signed jointly by Stephanie Crowe (ASD), Rajiv Gupta (CSE), Catriona Robinson (GCSB), Richard Horne (NCSC), David Imbordino (NSA), and Nick Andersen (CISA). The framing is unambiguous: frontier AI models are expected to exceed current industry expectations, and the timeline for that shift is not years, it is months.

This is not an isolated warning. Five days before the statement was published, NCSC CEO Dr Richard Horne told the Royal United Services Institute’s Annual Security Lecture that the NCSC had managed more than 200 cyber incidents affecting the UK’s critical national infrastructure in the year to May 2026, with around 75% believed linked to hostile state actors including Russia, China, and Iran [2]. Horne went further, arguing that cyber security should no longer be framed as a risk to be tolerated within appetite, but as an ongoing contest with capable adversaries. He also pointed to an NCSC assessment that by 2028, AI-enabled capabilities will likely be used to exploit known vulnerabilities in legacy technology at scale across UK critical infrastructure.

That assessment builds directly on guidance the NCSC published in May 2026, warning organisations to prepare for a “vulnerability patch wave”: a forced correction in which AI-accelerated exploitation surfaces decades of accumulated technical debt across commercial, open source, and proprietary software simultaneously [3]. The Five Eyes statement should be read as the international consolidation of that warning, not a standalone development.

What Does the Statement Set Out?

The statement is short and deliberately free of new technical detail. Its purpose is to compress urgency into a small number of leadership-level actions, structured around four overarching asks and five practical steps [1].

Leaders are urged to:

  • Understand and assess risk, readiness, and accountability. Boards need a clear, current picture of organisational exposure, not a static risk register reviewed annually.
  • Prioritise foundational cyber security practices and controls. Sophistication in tooling does not substitute for getting the fundamentals right.
  • Empower cyber leaders with authority and resources. Cyber leadership requires the mandate to act, not just the responsibility to report.
  • Stay actively engaged as threats and guidance evolve. Static governance models cannot keep pace with a threat landscape that is itself accelerating.

Two structural points distinguish this statement from prior Five Eyes guidance. First, it reframes AI not solely as an adversary capability but as a defensive obligation: organisations are explicitly told to use AI deliberately to strengthen defence, not merely to improve efficiency. Second, it sets an expectation that breaches are not preventable in absolute terms; preparedness is reframed as the capability to contain incidents quickly before they escalate into operational and financial crises [1].

Who is Affected by the Statement?

Boards and Executive Leadership

The statement is addressed primarily upward, not downward. It states plainly that cyber resilience is not an IT issue, it is central to operational continuity and market trust, and that it is not enough to have controls; leaders must be confident those controls will perform during a real incident [1]. This places direct accountability on boards and executives to verify resilience, not simply to fund it.

CISOs and Security Leadership

For security leaders, the statement is a mandate to escalate. The call to empower cyber leaders with authority and resources [1] gives CISOs a clear external reference point when seeking budget, headcount, or the organisational authority to challenge unsafe trade-offs that have previously been accepted in the name of operational convenience.

Operators of Critical National Infrastructure

For CNI operators, the statement reinforces direction already set domestically. The NCSC’s own intervention five days prior, disclosing that three-quarters of attacks on UK CNI are state-linked [2], makes clear that the threat described in the Five Eyes statement is not a future scenario for this sector. It is the current operating environment.

Vendors and Technology Providers

The statement explicitly calls on leaders across industry, including vendors, to act now [1]. Combined with the NCSC’s separate warning that a wave of vulnerability disclosures is approaching across commercial, open source, and proprietary software [3], vendors should expect both faster exploitation of existing flaws and intensifying customer expectations around patch velocity and secure-by-design practice.

What are the Key Challenges Organisations Will Face?

Compressed Exploitation Timelines

The central technical claim underpinning the statement is that AI is shrinking the window between vulnerability discovery and exploitation [1]. Patch cadences and change-management processes built around weeks or months of lead time were not designed for this. Organisations with manual patching processes, particularly across operational technology environments with long update cycles, face a widening gap between the speed of the threat and the speed of their own response.

Your Adversary Already Has an AI Upgrade

Even if your organization hasn’t touched AI, your attackers have. The patch window that once gave defenders breathing room is effectively gone — Mandiant’s time-to-exploit tracking shows exploits now landing on or before the day a CVE goes public. Exploitation itself has become a commodity: working proof-of-concept exploits can be generated in about 15 minutes, and autonomous vulnerability discovery campaigns can be run for roughly $50. This isn’t theoretical. Recovered logs from a June incident (via OALABS) showed a single operator driving over 1,000 AI-agent sessions across 14+ companies, with the models flagging a policy violation only about 10 times — because every request was simply framed as “authorized red-team” work. Social engineering has scaled right alongside it: Arup lost $25.6 million in 2024 after a video call where every “colleague” on the line was a deepfake, and the economics of that kind of attack have only gotten cheaper since. None of this requires exotic new attack vectors. It’s the same attack surface organizations have always had, now facing an adversary that doesn’t sleep, doesn’t hesitate, and operates at machine speed.

Legacy and Unsupported Systems

The statement is blunt that unsupported systems are not just technical debt, they are strategic liabilities [1]. This sits uncomfortably with sectors where legacy estate is structural rather than incidental, where replacement cycles are measured in years and safety-critical considerations constrain how quickly systems can be patched or retired.

Governance Gaps Between Boards and Technical Teams

Repeated emphasis on board-level accountability assumes a level of cyber literacy that many boards do not yet have. The gap between technical risk and the language boards use to govern it remains one of the most persistent obstacles to the kind of confident assurance the statement demands.

AI as a Dual-Use Capability

The statement’s insistence that organisations use AI deliberately to strengthen defence, not just improve efficiency [1], is a meaningfully higher bar than most organisations’ current AI security posture. Many security teams have adopted AI tooling for productivity gains. Far fewer have built the detection, monitoring, and response capability the statement envisages, while simultaneously managing the new attack surface that frontier AI systems themselves introduce.

Shipping Faster Means Shipping More Attack Surface

AI coding assistants have undeniably accelerated software delivery — but speed and security are moving in opposite directions. Veracode’s testing across more than 100 models found that roughly 45% of AI-generated code carries a security weakness. What’s more concerning is the trendline: functional correctness has raced past 95%, while the security rate has stayed flat at around 55% for two years running. Newer, smarter models are writing code that works — not code that’s safe. The practical impact is that attack surface is now growing at delivery speed, with code merging faster than any human review process was designed to handle, whether that code was sanctioned by the organization or introduced through shadow AI use, often with no clear provenance to trace it back. At the same time, client appetite for security testing is rising faster than budgets are — creating a widening gap between how much validation organizations want and how much they’re actually resourcing. Closing that appetite-budget gap is, in many ways, the central challenge facing security teams right now.

Zero-Day Proliferation

The statement warns directly that as AI systems evolve, new and previously unknown vulnerabilities will emerge, including zero-day vulnerabilities [1]. Defence-in-depth, rather than reliance on any single control or technology, is positioned as the only credible response to a vulnerability landscape that is itself becoming less predictable.

How IOActive Can Help

IOActive’s work across offensive security, operational technology and industrial control system (OT/ICS) assessment, and critical infrastructure advisory positions us to support organisations translating this statement’s leadership-level mandate into operationally credible defence. Testing, not assumption, is how organisations find out whether their controls will actually perform under pressure, which is precisely the bar the statement sets.

Red Team and Purple Team Services

The statement’s call to verify that controls will perform during a real incident, not merely exist on paper [1], is best answered through adversarial testing rather than compliance review. IOActive’s Red Team operations emulate the tactics of the threat actors most likely to target a given organisation’s sector and assets, while our Purple Team engagements translate offensive findings directly into measurable improvements in detection and response.

Full Stack Security Assessments

Reducing attack surface and accelerating patching, two of the statement’s five practical actions [1], both depend on first knowing where exposure actually sits. Our full stack assessments examine internet-facing systems, cloud environments, and on-premises infrastructure together, identifying the specific systems an attacker would prioritise rather than producing a generic vulnerability count.

Supply Chain Integrity

The statement’s call for action extends explicitly to vendors [1]. IOActive’s Supply Chain Integrity service assesses the security posture of technology providers and critical third parties, reviewing firmware, embedded systems, and procurement processes for inherited risk before it becomes either a compliance finding or an incident vector.

Preparedness and Resilience Testing

The statement’s framing of preparedness as a capability to be trusted, not assumed, aligns directly with our tabletop exercise and crisis simulation work. We help organisations stress-test detection, escalation, and recovery processes ahead of a real incident, building the operational muscle memory boards are now being asked to assure.

Threat Modeling and Advisory

Understanding and assessing risk, readiness, and accountability, the statement’s first call to action [1], requires a structured, evidence-based view of organisational exposure. Our threat modelling and advisory engagements give CISOs and boards a shared, prioritised picture of risk that can be acted on with confidence rather than debated indefinitely.

The statement is explicit that delay carries growing and avoidable risk [1]. We recommend the following immediate actions.

  1. Brief your board now on the statement’s core claim, that cyber risk assumptions can become outdated in months, and translate that into business, financial, and reputational terms.
  2. Map your patch and change-management cycle against the compressed exploitation timelines the statement describes, identifying where current processes cannot keep pace.
  3. Inventory legacy and unsupported systems with explicit reference to their exposure on external attack surfaces, not just their internal criticality.
  4. Review identity and access controls across critical systems, with particular attention to permissions that have accumulated without recent review.
  5. Test your incident response plan through a structured exercise that assumes a breach has already occurred, rather than one that tests whether it can be prevented.
  6. Evaluate how AI is currently used across your security function, distinguishing tools adopted for efficiency from capability genuinely built to strengthen detection and response.

Conclusion

The Five Eyes statement is short by design, but its brevity should not be mistaken for limited weight. Six of the world’s most authoritative cyber security agencies have chosen to speak with one voice, in plain language, to say that the basis on which most organisations currently assess cyber risk is already out of date.

The statement does not introduce new technical obligations. It does something arguably more consequential: it removes the option of treating AI-accelerated cyber risk as a future planning consideration. Combined with the NCSC’s own recent disclosures on the scale of state-linked attacks against UK critical infrastructure and the coming vulnerability patch wave, the message to leaders is consistent and increasingly difficult to defer.

Organisations that wait for a forcing event, whether a breach, a regulatory deadline, or a sector-specific mandate, will be acting from a position of weakness. Those that act now, testing their assumptions rather than reviewing them, will be the ones still standing when the window the statement describes finally closes.

If you would like to discuss how your organisation’s current posture measures up against the expectations set out in this statement, or how IOActive can support your cyber resilience programme, we welcome the conversation.

References

[1] Australian Signals Directorate, Communications Security Establishment, Government Communications Security Bureau, National Cyber Security Centre (UK), National Security Agency, Cybersecurity and Infrastructure Security Agency. The AI Shift in Cyber Risk: Why Leaders Must Act Now. 22 June 2026. https://www.ncsc.gov.uk/news/the-ai-shift-in-cyber-risk-why-leaders-must-act-now

[2] National Cyber Security Centre. NCSC CEO: Hostile States Linked to Three-Quarters of Cyber Attacks Affecting UK’s Critical Systems. 17 June 2026. https://www.ncsc.gov.uk/news/ncsc-ceo-hostile-states-linked-to-three-quarters-of-cyber-attacks

[3] National Cyber Security Centre. Preparing for a ‘Vulnerability Patch Wave’. 1 May 2026. https://www.ncsc.gov.uk/blogs/prepare-for-vulnerability-patch-wave