INSIGHTS | October 23, 2026

Below the Threshold: Why Britain’s Smallest Power Generators Face a Four-Year Cyber Security Gap

Key Takeaways

  • A small-scale gas generator was taken offline for four days in July 2026. The UK Government confirmed the incident but has not formally attributed it. [1]
  • Under the Network and Information Systems Regulations 2018, electricity generation is captured only at 2GW cumulative capacity, and the threshold expressly excludes generators that are not connected to a transmission system. [2]
  • On 5 August 2026 the Department for Energy Security and Net Zero and Ofgem confirmed that baseline cyber resilience requirements for all Ofgem licensees will be built on Cyber Essentials Plus, consulted on during 2027 and in place across the sector by the end of 2030. [3]
  • The same government response acknowledges that Cyber Essentials Plus excludes operational technology and lacks controls covering governance, incident response, risk management and supply chain. Its Plus tier applies the same five technical controls as Cyber Essentials with independent testing, rather than extending them. [3] [9]
  • IT and OT segregation was the single most requested additional control among consultation respondents, raised by 18 of the 49 organisations and individuals who replied. [3]

Why This Matters Now

In July 2026 a small-scale British generating asset stopped producing power for four days following a cyber incident. Michael Shanks, Minister of State at the Department for Energy Security and Net Zero, confirmed that the incident had affected a small-scale energy generator, and the Department stated that at no point was the wider energy system at risk. [1] Press reporting linked the intrusion to Iranian-aligned actors, though the UK Government has made no formal attribution.

The detail that matters for security leaders is not the attribution. It is the position of the asset. A four-day outage at a small distribution-connected generator is an outage at something well below the regulatory perimeter drawn in 2018, which means the operator was almost certainly under no statutory cyber resilience obligation at all.

That perimeter is not a historical accident. The Government’s own Energy Sector Cyber Security Strategy states that the NIS Regulations were only ever intended to apply to the most critical operators and therefore do not provide holistic coverage of the energy system. [4] The strategy also commits Government to encourage more reporting of cyber incidents that fall below NIS thresholds, which is a plain acknowledgement that the sub-threshold estate is a blind spot.

The threat is not theoretical. In December 2025 a threat actor targeted around 30 distributed renewable assets in Poland, including wind and solar farms and a combined heat and power plant. Generation and heat supply held, and the plant involved served nearly 500,000 heat customers. What matters is how the attacker got in: internet-exposed firewall appliances without multi-factor authentication, unpatched devices and reused credentials. Most of those routes could have been closed by basic cyber hygiene. A parallel attack the same day on a smaller plant serving 50,000 residents did interrupt cogeneration, shutting down a steam turbine and the water treatment system. [5] [6]

Meanwhile the estate is growing. Government projections cited in the March 2026 consultation put battery storage capacity on a six-fold increase and wind and solar capacity almost tripling by 2030. [5] Ofgem currently regulates just over 1,400 licensed operators, and Government has described the absence of cyber resilience requirements across a large proportion of them as one of two fundamental reform needs. [3]

What the Regulatory Position Actually Is

Schedule 2 of the NIS Regulations 2018 sets the thresholds at which an operator becomes an Operator of Essential Services. For downstream gas and electricity these are as follows.

Essential ServiceElectricityGas (Downstream)
Generation2GW or more (cumulative)N/A
TransmissionMore than 250,000 final customersMore than 250,000 final customers
Offshore Transmission2GW or more (cumulative)N/A
DistributionMore than 250,000 final customersMore than 250,000 final customers
Interconnectors1GW or moreMore than 20M m3 gas per day
SupplyMore than 250,000 final customersMore than 250,000 final customers
Load Control300MW or moreN/A

Source: DESNZ and Ofgem consultation documents, drawn from NIS Regulations 2018 Schedule 2. Generation excludes nuclear generators and generators not connected to a transmission system. Capacity is cumulated across affiliated undertakings. Load control is not yet in force and will be commenced through the Cyber Security and Resilience Bill. [2] [3]

Two features of that table deserve attention. First, generation capacity is cumulated across a corporate group, so a modest site inside a large portfolio can sit above the line while a standalone site of identical rating sits below it. Second, generators not connected to a transmission system are carved out regardless of size, which removes most distribution-connected embedded generation from scope entirely.

Government consulted on this between 27 March and 22 May 2026 and published its response on 5 August 2026. Nineteen respondents told Government that the electricity generation threshold should change. Twenty-one argued that thresholds should be driven by risk or impact rather than by supply or generation volume, and 19 said the sector has become distributed to the point where current thresholds no longer reflect where risk arises. Six respondents proposed specific replacement figures, including 200MW and 500MW for generation. [3]

Government has not adopted a new number. It has commissioned the National Energy System Operator to advise on which services and thresholds should apply, and intends to consult on any revisions during 2027, subject to the Cyber Security and Resilience Bill receiving Royal Assent. The response states that Royal Assent is expected in early 2027, though secondary coverage consistently reports an expectation of late 2026. The Bill completed Lords Second Reading on 14 July 2026 and entered Lords Committee Stage on 1 September 2026. [3] [8]

Alongside that review, Government confirmed it will introduce baseline cyber resilience requirements for all Ofgem licensees, delivered through licence conditions and founded on Cyber Essentials Plus. Ofgem will consult on the detail during 2027. The public commitment is that a baseline level of cyber resilience will be in place across the whole downstream gas and electricity system by the end of 2030. Any intermediate tier between baseline and NIS is expected to be considered only after 2030. [3]

Who is Affected by the Sub-Threshold Gap?

Sub-threshold generators and distributed energy operators. Operators of embedded gas plant, solar, onshore wind, battery storage and long duration storage that fall below 2GW, or that are not transmission-connected, carry no statutory cyber resilience obligation today and will carry none until baseline requirements are implemented through licence conditions. Many of these sites are unmanned and dependent on remote access.

NIS-designated operators. Designation does not insulate a large operator from the gap. NIS requirements apply only to the network and information systems on which the essential service relies, which Government acknowledges leaves ancillary, supporting and back-end systems outside scope. [5] Large operators also depend on smaller counterparties for flexibility, balancing and aggregation.

Aggregators, flexibility platforms and remote service providers. Consultation respondents identified flexibility services, aggregators and orchestration platforms as the most commonly proposed additions to the essential services list, alongside digital and data platforms and remote monitoring and management providers. [3] Some of these organisations will be captured as large load controllers at 300MW of aggregate controllable load. Many will not.

Boards and investors in generation assets. The regulatory floor is now dated and public. A board that waits for 2030 is accepting four years of exposure on an asset class that has already been taken offline once.

What Are the Challenges the 2030 Baseline Does Not Solve?

The most significant issue is that the announced remedy is shaped for information technology, not for the control systems that took the plant offline.

Government has been candid about this. The consultation observed that Cyber Essentials is primarily suitable for IT, that many downstream gas and electricity operators rely on SCADA systems, programmable logic controllers, human machine interfaces and remote telemetry units, and that applying Cyber Essentials controls to those environments can be challenging and in certain circumstances unsuitable. [5] The government response goes further, recognising that Cyber Essentials Plus has limitations for the energy sector in relation to the exclusion of operational technology and the absence of controls for governance, incident response, risk management and supply chain. [3]

Respondents said the same thing with numbers behind it. IT and OT integration or network segmentation was the leading requested addition at 18 respondents, followed by incident response and exercising at 17, remote access management at 13, supply chain visibility at 12 and governance at 10. When asked for alternative frameworks, respondents most often named the NCSC Cyber Assessment Framework at 16 and IEC 62443 at 15, ahead of ISO 27001 at 14. [3] The sector asked for an OT-aware standard. What has been confirmed so far is an IT scheme that Government intends to build on, with the additional controls still to be designed. It is worth being precise about what the Plus tier adds: Cyber Essentials Plus applies the same five technical controls as Cyber Essentials and subjects them to independent technical testing rather than extending them. [9] Choosing Plus over the base scheme raises the assurance level, not the scope.

Three further constraints compound this. Government intends that, where possible, baseline requirements should apply only to systems not already covered by existing cyber resilience obligations, which creates scope boundaries that operators will need to evidence rather than assume. [3] Consultation respondents reported that the prescriptiveness of Cyber Essentials controls and the inability to use compensating controls were common drivers of cost in OT-heavy and legacy environments. [3] And the assurance route for complex estates is still under exploration, with Government committing only to examine the potential of NCSC Cyber Essentials Pathways. [3]

The practical conclusion for a security leader is that compliance and resilience are not the same programme here, and neither of them arrives before 2030.

How IOActive Can Help

The gap this post describes is not a compliance problem yet, which is precisely why it is an assessment problem now. An operator below the 2GW line has no licence condition to evidence against and no NIS designation to scope, so the only reliable way to establish its position is to test the estate against a framework the eventual baseline will have to catch up to.

IOActive has operated in industrial control environments since building the first proof-of-concept worm against the smart grid in 2009 [10], and has helped define standards and best practices including NIST 800-53 and 800-37. The services below map to the specific gaps the 2030 baseline leaves open.

Full Stack Security Assessments

Government has confirmed that Cyber Essentials Plus excludes operational technology and that applying its controls to SCADA systems, programmable logic controllers, human machine interfaces and remote telemetry units can be unsuitable. Our Full Stack assessments examine the whole environment rather than a single layer, covering the controllers and HMIs at distribution-connected sites, the OT/IT boundary, and the cellular and vendor paths that commonly provide unmanned generation assets with connectivity nobody has inventoried. Where the baseline will eventually ask for evidence, an assessment produces it rather than assuming it.

Hardware and Firmware Security Research

The assets in question are largely unmanned and remotely operated, which places the security of the controller and telemetry unit itself in scope rather than only the network around it. Our hardware and firmware research examines the devices deployed at these sites directly, at a depth that network-layer testing cannot reach and that no IT-derived certification scheme currently asks for.

Supply Chain Integrity

Consultation respondents named supply chain visibility among the leading controls missing from Cyber Essentials Plus, and identified aggregators, flexibility platforms and remote monitoring providers as the additions most often proposed to the essential services list. Our Supply Chain Integrity work assesses the posture of technology providers and critical third parties, covering firmware, embedded systems, remote access arrangements and procurement, so that inherited risk is identified before it becomes a shared incident. For operators contracting with aggregators and remote service providers, this is the exposure that sits outside their own perimeter and inside their own outage.

Red Team and Purple Team Services

Incident response and exercising was the second most requested addition to the baseline, at 17 respondents. Adversary simulation is how an operator establishes whether an intrusion at a small asset would be detected and contained before it interrupts generation, rather than assuming the segmentation on the network diagram holds under test.

Advisory Services

The 2027 consultations will ask operators to state which systems fall inside a future baseline, which already sit inside NIS scope, and where residual OT exposure lies. That is a scoping determination an operator has to be able to defend, not describe. Our Advisory Services cover programmatic security review, security programme development and management, and Virtual CISO support, and the output is a documented scope position for each asset, a remediation sequence with named owners and dates, and the evidence pack a board or regulator will ask for.

If you would like to discuss where your generation or distributed energy assets sit against the thresholds described in this post, and what the residual OT exposure looks like, we welcome the conversation.

  1. Establish the regulatory position of every generating asset in the portfolio, including cumulative group capacity and whether the connection is to a transmission or a distribution system, and record the basis for each determination.
  2. Treat the 2030 baseline as a floor rather than a target, and assess the estate against an OT-aware framework such as IEC 62443 or the NCSC Cyber Assessment Framework rather than waiting for licence conditions to be drafted.
  3. Inventory remote access into unmanned sites, including vendor and maintenance pathways, and verify that segmentation between corporate IT and control networks holds under test rather than on the network diagram.
  4. Extend incident response plans to cover loss of generation at a sub-threshold asset, and exercise them, given that incident response and exercising was the second most requested control in the consultation.
  5. Review contractual cyber security obligations with aggregators, flexibility platforms and remote monitoring providers, several of which may be brought into NIS scope during the 2027 review.
  6. Engage with the Ofgem consultation expected during 2027, since the additional controls that sit above Cyber Essentials Plus are still being designed and sector evidence will shape them.

Conclusion

The regulatory perimeter for British electricity generation was drawn around a small number of very large assets in 2018, for an energy system that no longer exists. Government has recognised this, commissioned advice on where the line should move, and committed to a baseline for every Ofgem licensee by the end of 2030. That work is welcome and it is also four years away, and the scheme chosen as its foundation does not currently reach operational technology.

Operators that have already been targeted do not have four years, and press analysis published a month after the incident concluded that Britain’s small power plants face continued cyber risk. [7] The organisations that come through the next phase in good order will be those that treat the 2030 baseline as the minimum they will eventually be asked to evidence, and build OT security ahead of it on their own timetable.

References

  1. The Register, “Iran-linked cyberattack shut down a UK power plant”, 24 August 2026, carrying the Department for Energy Security and Net Zero statement on the small-scale energy generator incident. https://www.theregister.com/security/2026/08/24/iran-linked-cyberattack-shut-down-a-uk-power-plant/ First reported by The Sunday Telegraph, 22 August 2026 (paywalled).
  2. The Network and Information Systems Regulations 2018, Schedule 2, U.K. Essential Services and Threshold Requirements. https://www.legislation.gov.uk/uksi/2018/506/schedule/2 (revised text as in force at 2 September 2026).
  3. Department for Energy Security and Net Zero and Ofgem, “Reshaping cyber regulation in downstream gas and electricity: government response”, 5 August 2026. https://www.gov.uk/government/consultations/whole-energy-cyber-resilience-requirements-reshaping-cyber-regulation-in-downstream-gas-and-electricity
  4. Department for Energy Security and Net Zero, Ofgem, NCSC and NESO, “Energy Sector Cyber Security Strategy”, 28 May 2026. https://www.gov.uk/government/publications/energy-sector-cyber-security-strategy/energy-sector-cyber-security-strategy
  5. Department for Energy Security and Net Zero and Ofgem, “Reshaping cyber regulation in downstream gas and electricity: consultation document”, 27 March 2026. https://assets.publishing.service.gov.uk/media/69c51142471d520038d0f68d/whole-energy-resilience-consultation-document.pdf
  6. CERT Polska, “Energy Sector Incident Report – 29 December”, published January 2026. https://cert.pl/en/posts/2026/01/incident-report-energy-sector-2025/ (full report: https://cert.pl/uploads/docs/CERT_Polska_Energy_Sector_Incident_Report_2025.pdf). See also CERT Polska, “Follow-Up Report of the December 2025 Energy Sector Incident”, August 2026. https://cert.pl/en/posts/2026/08/incident-follow-up-report-energy-sector-2025/
  7. The Guardian, “UK’s small power plants face continued cyber risk after Iran-linked hack”, 27 August 2026. https://www.theguardian.com/business/2026/aug/27/uk-small-power-plants-risk-cyber-attacks-iran-hack
  8. Cyber Security and Resilience (Network and Information Systems) Bill, HL Bill 32, introduced to Parliament 12 November 2025. Lords Second Reading 14 July 2026, Lords Committee Stage from 1 September 2026. https://bills.parliament.uk/bills/4035
  9. National Cyber Security Centre, Cyber Essentials. https://www.ncsc.gov.uk/cyberessentials/overview
  10. M. Davis, IOActive, “Advanced Metering Infrastructure (Smart Grid) Device Security”, Black Hat USA 2009. https://blackhat.com/presentations/bh-usa-09/MDAVIS/BHUSA09-Davis-AMI-SLIDES.pdf
INSIGHTS | September 25, 2026

One Exposure, Many Actors: What the NCSC’s OT Alert Adds to the AA26-097A Picture

Key Takeaways

  • On 27 August 2026, the NCSC published an Alert warning of increased targeting of operational technology (OT) systems across multiple sectors globally, including in the UK, carried out by a range of threat actors and resulting in some limited real-world disruption [1].
  • The Alert is deliberately unattributed. It should not be read as an extension of joint advisory AA26-097A, which attributes a separate and well-documented PLC exploitation campaign to Iranian-affiliated actors [2].
  • Three separate bodies of reporting published between April and August 2026, covering Iranian-affiliated PLC exploitation, Russian FSB Centre 16 router targeting, and unattributed activity against water sector controllers, converge on the same access route of systems reachable directly from the public internet.
  • The FBI and EPA have reported that similarities in network configurations supplied by third parties allowed attackers to repeat successes across multiple victims, making integrator and supplier architecture a first-order concern rather than a downstream one [3].
  • The Alert lands five days before the UK Cyber Security and Resilience Bill reaches Lords Committee Stage on 1 September 2026, placing OT exposure in front of regulators, boards and legislators simultaneously [4].

Why the NCSC’s Alert Matters Now

The NCSC classified its 27 August publication as an Alert rather than guidance. That distinction carries weight. The organisation states that it has been engaging with affected sectors directly in response to recent targeting and is publishing the material to support national resilience efforts, which indicates that the advice follows live incident handling rather than horizon scanning [1].

The substance is uncomfortable for anyone who has treated OT exposure as a solved problem. The NCSC reports increased targeting of OT systems across multiple sectors globally, including in the UK, conducted by a range of threat actors, with some limited real-world disruption already recorded [1]. It also sets out a broader judgement. Against a backdrop of technology-enabled uplifts in offensive capability and increased geopolitical instability, the threat from state use of offensive cyber, including outside of conflict, has almost certainly increased [1].

The timing compounds the message. The Alert arrives within four months of joint advisory AA26-097A, seven weeks after an international advisory on Russian state targeting of network devices, and four weeks after an FBI and EPA announcement describing degraded water operations in at least seven US states [2][3][5]. Regulators are moving in parallel. The Cyber Security and Resilience Bill is scheduled to enter Lords Committee Stage on 1 September 2026, with Royal Assent expected later in the year [4].

What Does the NCSC Alert Actually Say?

The Alert sets out eight actions. Several restate established practice:

  • Build a definitive view of OT architecture including all assets, communications pathways and external connections
  • Replace default credentials and enforce unique administrator accounts with multi-factor authentication where supported
  • Harden the OT boundary and keep gateways, firewalls, routers and remote access appliances within vendor support
  • Segment OT, management and business networks
  • Maintain tested, ransomware-resistant backups of configurations, controller logic and critical engineering data [1]

Two items deserve closer attention because they move beyond network-layer control.

The first concerns device state. The NCSC advises that OT devices be operated in a condition that prevents remote programming during normal operations, ensuring PLCs are not left in PROGRAM or other maintenance modes and that controller logic uses password-based write protection or equivalent mechanisms to prevent unauthorised changes from malicious endpoints [1]. This is a control on the device itself, not on the path to it, and it assumes the network boundary may fail.

The second concerns protocols. The Alert recommends migrating industrial protocols to secure variants where available, naming DNP3 to DNP3-SAv5, CIP to CIP Security, Modbus to Modbus Security, and OPC DA to OPC UA, while removing telnet and SNMP versions 1 and 2 from management use [1]. Where no secure alternative exists, insecure protocols should be confined to isolated network segments.

The Alert also addresses organisations without OT estates, noting a continuing pattern of disruptive activity against internet-exposed systems and edge devices across all sectors, and directing readers to maintain an accurate inventory of internet-facing systems, retire end-of-life equipment and monitor for unexpected configuration changes or outbound connections [1]. It points UK organisations towards the NCSC’s free Early Warning service and frames the Cyber Assessment Framework as the mechanism through which boards should seek assurance [1].

Notably, the Alert names no threat actor.

How Does This Connect to AA26-097A, and Where Does It Not?

This is the point at which analysis most often goes wrong, and the distinction matters more than the similarity.

Advisory AA26-097A, first published on 7 April 2026 and updated on 22 July 2026, attributes an active campaign to Iranian-affiliated APT actors exploiting internet-connected PLCs across US critical infrastructure. The July update broadened the observed manufacturer scope from Rockwell Automation/Allen-Bradley to include Schneider Electric and Siemens controllers, added detection guidance for malicious changes in reusable code modules within Rockwell PLC programs, and brought the Department of the Treasury onto the authoring byline alongside CISA, the FBI, NSA, EPA, the Department of Energy and US Cyber Command’s Cyber National Mission Force [2].

Separately, an international advisory published in July 2026, co-sealed by the NCSC alongside 18 partner agencies from 12 countries, attributes sustained targeting of poorly configured routers to Russian Federal Security Service Centre 16, tracked variously as Berserk Bear, Energetic Bear, Dragonfly, Ghost Blizzard and Static Tundra. That activity centres on internet-wide scanning for devices accepting default or weak SNMP community strings, followed by exfiltration of device configuration files [5].

Separately again, the FBI and EPA issued a public service announcement on 30 July 2026 describing unattributed malicious cyber actors targeting internet-facing Rockwell Automation/Allen-Bradley MicroLogix 1100 and 1400 PLCs. Water and wastewater utilities in at least seven states reported incidents from 27 July 2026 onwards. The actors changed device IP addresses and set passwords, producing loss of view and, in some cases, loss of function. Reported operational effects included loss of pressure and flooding, with the announcement noting that pressure loss in water systems could potentially allow untreated groundwater to seep into pipes [3].

Four publications carry three different attribution states. One names Iranian-affiliated actors, one names a Russian intelligence unit, and two describe activity the authoring agencies have chosen not to attribute. Collapsing these into a single narrative would be an analytical error, and one that regulated operators cannot afford to make in reporting or board briefings.

What survives the separation is the access route. In every case the initial condition is the same, namely a control system, a management interface or an edge device reachable from the public internet and frequently protected by default, weak or absent credentials. The NCSC’s phrasing, that this activity is being carried out by a range of threat actors, is the more useful framing for defenders precisely because it removes the actor from the risk calculation. Exposure is exploitable by whoever finds it first.

Who is Affected by the NCSC’s OT Alert?

CNI operators with field-deployed OT

Any organisation with internet-exposed OT could be affected. The NCSC is explicit that organisations should not assume their OT is inaccessible from the internet without verifying it, since unintended exposure can arise through misconfigurations, legacy connections or unmanaged assets [1]. Water, wastewater and energy operators with geographically distributed sites and cellular field connectivity carry the highest concentration of this risk.

System integrators and managed service providers

The FBI and EPA observed that across several victims, similarities in network setups provided by third parties may give attackers the opportunity to multiply successes where vulnerable configurations recur across a supplier’s customer base [3]. A single integrator’s default deployment pattern becomes a repeatable attack template. This finding maps directly onto the critical supplier designation powers in the Cyber Security and Resilience Bill.

Organisations without OT

The Alert is explicit that the broader pattern of disruptive activity against internet-exposed systems and edge devices affects all sectors [1]. Routers, firewalls, VPN concentrators and remote access appliances present the same fundamental exposure.

Boards and regulated entities across jurisdictions

UK operators face the CAF as the assurance framework of record and the Cyber Security and Resilience Bill as the coming statutory instrument [1][4]. EU operators are working to NIS2. US operators sit within the CISA advisory and directive framework, including binding requirements on end-of-support edge devices [6]. The technical remediation is common across all three, and only the reporting obligations differ.

What Makes This Exposure So Difficult to Eliminate?

The mitigations in the NCSC Alert are not novel, and that is the difficulty. Every one of the eight actions was recognised practice before August 2026. Their repeated publication indicates a gap between recommendation and implementation rather than a gap in knowledge.

Three factors sustain that gap.

Asset visibility remains hard in OT. Exposure is frequently unintended, arising from a commissioning shortcut, a supplier’s remote support link, or a cellular modem installed to solve an operational problem years earlier. An operator can hold an accurate architecture diagram and still be exposed through an asset that diagram never captured.

Integrity attacks defeat availability-focused monitoring. AA26-097A describes actors using legitimate vendor engineering software to alter controller logic and falsify operator displays, and the FBI reported at least one organisation discovering modified PLC project files after noticing ladder logic discrepancies across several sites [2][3]. Where the control room’s picture of the process is itself manipulated, conventional uptime monitoring will report normality.

Remediation carries operational cost. Removing a PLC from direct internet exposure, migrating a protocol, or replacing an end-of-life gateway involves planned downtime in environments where downtime is the primary risk being managed. This is where technical recommendation meets capital planning, and where accountability for the outcome frequently disperses.

How IOActive Can Help

The NCSC’s Alert describes a condition rather than an incident. That condition is assets reachable from the internet that the owner did not know were reachable, protected by credentials the owner did not know were still default. Verifying that condition is an assessment problem before it is a remediation problem, and it spans the OT estate, the edge estate and the third parties with standing access to both.

IOActive has operated in industrial control environments since building the first proof-of-concept worm against the smart grid in 2009 [9], and has helped define standards and best practices including NIST 800-53 and 800-37. The services below map to the specific gaps this Alert exposes.

Full Stack Security Assessments

The Alert’s first action, to build a definitive view of OT architecture and not assume OT is unreachable without verifying it, is precisely the work most assessments stop short of. Our Full Stack assessments examine the whole environment rather than a single layer, covering internet-facing controllers and HMIs, the OT/IT boundary, the cellular modem paths that frequently provide field sites with their only route to the internet, and the firmware and silicon of the devices themselves through penetration testing, reverse engineering, side-channel analysis and fault injection.

Two of the Alert’s actions sit at the device rather than the network layer. Those are confirming controllers are not left in PROGRAM mode, and migrating industrial protocols to secure variants such as DNP3-SAv5, CIP Security, Modbus Security and OPC UA. These are testable conditions, not policy statements, and they are where an assessment either produces evidence or produces reassurance. As we set out in Cyber Attack Trends 2026, the environments organisations depend on most are routinely the ones they monitor least.

Supply Chain Integrity

The FBI and EPA finding that similar third-party network configurations allowed attackers to repeat successes across a supplier’s customer base is the most consequential detail in the current reporting, and the least addressable by any single operator acting alone [3]. It also has a direct precedent in our analysis of the Polish energy sector incident, which documented more than 30 facilities breached through the same pattern of internet-facing VPN portals without MFA, where credential reuse across sites turned one compromised account into a fleet-wide problem.

Our Supply Chain Integrity work assesses the security posture of technology providers and critical third parties, covering firmware, embedded systems, remote access arrangements and procurement processes, so that inherited risk is identified before it becomes a shared incident. For UK operators, this maps onto the critical supplier designation powers in the Cyber Security and Resilience Bill [4].

Red Team and Purple Team Services

The Alert notes that OT environments are typically static and predictable, which makes baseline monitoring highly effective at identifying unauthorised activity [1]. The question is whether a given deployment actually achieves that in practice. Adversarial testing is how an operator finds out before an adversary does, particularly against integrity attacks such as altered controller logic and falsified operator displays, which availability-focused monitoring is not built to catch. Our Purple Team work translates those findings into measurable detection improvements, and we set out the distinction between the two approaches in Red Team vs Penetration Testing.

Advisory Services

The eight actions in this Alert have all been published before, in various forms, and that is the problem worth solving. When we examined the Minnesota water utilities in When the Advisory Arrives First, the gap was not the absence of a warning but the absence of an owner for acting on it.

Our Advisory Services cover programmatic security review, security programme development and management, and Virtual CISO support. They turn an alert into a prioritised remediation plan with named accountability, and produce the evidence boards need for CAF or equivalent regulatory assurance. That work is increasingly shaped by converging regimes across all three jurisdictions, as we examined in our analysis of the UK Energy Sector Cyber Security Strategy and the Five Eyes statement on AI and cyber risk. The latter is directly relevant to the NCSC’s judgement here that technology-enabled uplifts in capability are part of why the threat has increased [1].

If you would like to discuss how your organisation’s internet-facing OT and edge exposure measures up against the activity described in this Alert, we welcome the conversation.

  1. Verify exposure rather than assuming its absence. Build or refresh a definitive view of the OT architecture covering all assets, communications pathways and external connections, and validate it against external scanning results rather than against documentation [1].
  2. Remove control system devices from direct internet reachability. Broker all remote access through a secure gateway or jump host so that OT is never directly exposed to external networks, and secure cellular modems used for field connectivity with strong authentication and logging [1][3].
  3. Eliminate default and shared credentials on OT and edge devices. Enforce unique administrator accounts, enable multi-factor authentication where supported, and use key-based authentication in preference to passwords where the protocol allows [1].
  4. Enforce device-level write protection. Confirm that PLCs are not left in PROGRAM or maintenance modes during normal operations and that controller logic is protected against unauthorised modification [1].
  5. Validate controller logic integrity. Use vendor integrity checking tools to compare running programs against known-good logic, and verify that backups are free of malicious logic before restoration [3].
  6. Retire or isolate end-of-support edge devices. Maintain a rolling replacement forecast reviewed against ownership and procurement, and apply compensating controls with firm decommission dates where replacement is delayed [3][6].
  7. Baseline and monitor OT network traffic. OT environments are typically static and predictable, which makes baseline monitoring effective at identifying communication with PLCs and HMIs from unexpected devices, networks or routes [1].
  8. Rehearse manual operation and recovery. Test the capability to revert to manual control, isolate affected systems and restore from trusted backups, and treat those exercises as evidence for CAF or equivalent regulatory assurance [1][3].

Conclusion

The NCSC’s August Alert does not describe a new technique, a new vulnerability class or a new adversary. It describes a durable condition that a widening set of actors continues to find and exploit, namely control systems and edge devices reachable from the open internet. The value in reading it alongside AA26-097A is not in merging the two, but in observing that campaigns with entirely different sponsors, objectives and levels of sophistication are arriving at the same door.

That has a practical consequence for how operators prioritise. Attribution shapes the diplomatic and sanctions response, but it does not change the remediation. An internet-facing PLC with a default password represents identical risk whether the entity that finds it is a state intelligence service or an opportunistic scanner. As the UK’s statutory regime moves towards Royal Assent and the EU and US frameworks tighten in parallel, the operators best positioned will be those who can evidence what they expose to the internet, and who owns the answer.

References

  1. National Cyber Security Centre, Disruptive cyber activity highlights risk from internet-exposed systems and edge devices, 27 August 2026. https://www.ncsc.gov.uk/news/disruptive-cyber-activity-highlights-risk-from-internet-exposed-systems-and-edge-devices
  2. CISA, FBI, NSA, EPA, DOE, US Cyber Command CNMF and Department of the Treasury, Joint Cybersecurity Advisory AA26-097A, Iranian-Affiliated Cyber Actors Exploit Programmable Logic Controllers Across US Critical Infrastructure, published 7 April 2026, updated 22 July 2026. https://www.cisa.gov/news-events/cybersecurity-advisories/aa26-097a
  3. Federal Bureau of Investigation and Environmental Protection Agency, Malicious Cyber Actors Targeting Water and Wastewater Sector Internet-Facing Programmable Logic Controllers, Causing Operational Disruptions, 30 July 2026. https://www.fbi.gov/investigate/cyber/alerts/2026/malicious-cyber-actors-targeting-water-and-wastewater-sector-internet–facing-programmable-logic-controllers-causing-operational-disruptions
  4. UK Parliament, Cyber Security and Resilience (Network and Information Systems) Bill, HL Bill 32, Lords Second Reading 14 July 2026, Committee Stage 1 September 2026. https://bills.parliament.uk/bills/4035
  5. National Cyber Security Centre, UK and Allies urge critical sectors to improve defences against Russian intelligence targeting, July 2026. https://www.ncsc.gov.uk/news/uk-and-allies-urge-critical-sectors-to-improve-defences-against-russian-intelligence-targeting
  6. CISA, Reducing the Attack Surface for End-of-Support Edge Devices and Binding Operational Directive 26-02. https://www.cisa.gov/resources-tools/resources/reducing-attack-surface-end-support-edge-devices
  7. NCSC-UK, FBI and CISA, Secure Connectivity Principles for Operational Technology. https://www.ncsc.gov.uk/collection/operational-technology/secure-connectivity
  8. National Cyber Security Centre, Cyber Assessment Framework. https://www.ncsc.gov.uk/collection/cyber-assessment-framework
  9. M. Davis, IOActive, Advanced Metering Infrastructure (Smart Grid) Device Security, Black Hat USA 2009. https://blackhat.com/presentations/bh-usa-09/MDAVIS/BHUSA09-Davis-AMI-SLIDES.pdf